Plan Review Notes
Plan Review Notes For Permit 09020527
Permit Number 09020527
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-03 11:47:10****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE APPLICATION STATES THAT THE HOMEOWNER HAS
 EXISTING HURRICANE SHUTTERS. PLEASE PROVIDE A PERMIT
 NUMBER FOR THE EXISTING SHUTTERS; SHUTTERS ARE TO BE IN
 ACCORDANCE WITH FBC, SEE FBC R 301.2.1.2, FBC EB 507.
  
 2. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 3. ON THE FLOOR PLAN, SHOW THE LOCATION OF THE PROPOSED
 STRUCTURAL WORK.
  
 4. SCOPE OF WORK IS NOT CLEAR. THE "EXISTING FLOOR PLAN
 - REMODEL" STATES THAT THE "NEW SGD TO REMAIN." IF IT'S
 NEW, HOW CAN IT REMAIN?
  
 5. A SGD IS SHOWN AS "INFILL" ON AN ELEVATION, ANOTHER
 ELEVATION SHOWS A WALL WITH A WINDOW, BUT THE WALL
 DETAIL DOESN'T SHOW A WINDOW. THE DETAIL DOES NOT MATCH
 THE SCOPE OF WORK.
  
 6. THE WALL FRAMING SECTION DOES NOT SHOW FASTENING AT
 THE TOP OF THE WALL. THE ELEVATION SHOWS A WINDOW, BUT
 NO WINDOW (OR STRUCTURAL SUPPORT) IS SHOWN ON THE WALL
 FRAMING DETAIL.
  
 7. SHOW FINISHED FLOOR IN RELATION TO THE GRADE, FBC
 R404.1.6. IT APPEARS THAT THIS SCREENED AREA IS BEING
 CONVERTED TO INTERIOR SPACE.
  
 8. PALM BEACH COUNTY IMPACT FEE ASSESSMENT REQUIRED DUE
 TO INCREASE OF HABITABLE SPACE, 561-233-5025. THE PLANS
 MUST BE STAMPED AND THE RECEIPT, IF FEES ARE DUE,
 ATTACHED TO THE APPLICATION.
  
 9. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE INSTALLATION SCHEDULE OR SUBMIT
 ALL INFORMATION IN ANOTHER FORMAT.
  
 10. BOND BREAK REQUIRED, FBC703.6.3.1.
  
 11. SHOW COMPLIANCE WITH FBC704, INSPECTION FOR
 TERMINTES.
  
  
  
  
  
  