| Notes |
| Date |
Text |
| 2009-02-25 10:32:14 | 2004 FBC W/2007 REVISIONS | | | RE-ROOF | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND | | | DESIGN PRESSURE WILL BE USED TO INSTALL EACH OF THE | | | TAMKO MODIFIED ROOF SYSTEMS. CIRCLE THE APPROPRIATE ONE | | | ON THE NOA. | | | | | | 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C'. | | | SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING OF | | | THE BASE SHEET AS REQUIRED BY GENERAL LIMITATION # 7 ON | | | PAGE 18 OF THE NOA. | | | | | | 3) A SEPARATE PERMIT IS REQUIRED FOR THE SOLAR PANELS. | | | | | | 4) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. FS 713 | | | | | | 5) THE VALUE FOR THE WORK ON THE APPLICATION IS LOW AND | | | HAS BEEN ADJUSTED BASED ON MARSHALL AND SWIFT | | | VALUATION. ADDITIONAL PERMIT FEES OF $ 152.59 ARE DUE. | | | FBC 108.3* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|