2009-03-25 19:55:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO INFORMATION WAS PROVIDED REGARDING CHANGES TO THE
 EXISTING HVAC SYSTEM. PROVIDE DETAILED DRAWING SHOWING
 ANY CHANGES BEING MADE TO ACCOMODATE THE PROPOSED
 ALTERATION OF THESE SPACES IN ACCORDANCE WITH FBC-B
 106.1.1.
  
 2. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN THE
 NEWLY CREATED ROOMS IN ACCORDANCE WITH FBC-M 601.4.
  
 3. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DEFINED
 IN THE FBC-EB CHAPTER 2. SHOW COMPLIANCE WITH THE
 VENTILATION REQUIREMENTS FOR ALL RECONFIGURED SPACES IN
 ACCORDANCE WITH FBC-EB 709.1 AND FBC-M SECTION 402 OR
 SECTION 403.
  
 4. SEE FBC-B 106.1.3 FOR REQUIREMENTS RELATED TO
 QUALITY OF BUILDING PLANS SUBMITTED.
  