1 |
|
| Notes |
| Date |
Text |
| 2009-03-25 19:55:41 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO INFORMATION WAS PROVIDED REGARDING CHANGES TO THE | | | EXISTING HVAC SYSTEM. PROVIDE DETAILED DRAWING SHOWING | | | ANY CHANGES BEING MADE TO ACCOMODATE THE PROPOSED | | | ALTERATION OF THESE SPACES IN ACCORDANCE WITH FBC-B | | | 106.1.1. | | | | | | 2. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN THE | | | NEWLY CREATED ROOMS IN ACCORDANCE WITH FBC-M 601.4. | | | | | | 3. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DEFINED | | | IN THE FBC-EB CHAPTER 2. SHOW COMPLIANCE WITH THE | | | VENTILATION REQUIREMENTS FOR ALL RECONFIGURED SPACES IN | | | ACCORDANCE WITH FBC-EB 709.1 AND FBC-M SECTION 402 OR | | | SECTION 403. | | | | | | 4. SEE FBC-B 106.1.3 FOR REQUIREMENTS RELATED TO | | | QUALITY OF BUILDING PLANS SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|