| Date |
Text |
| 2009-05-07 16:27:39 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. IT IS NOT CLEAR HOW THIS DETAIL "SUPPORT SPACER" |
| | CORRELATES WITH THE PLAN. THIS IS LABELED SECTION A1, |
| | NO A1 ON THE PLAN, SO IS THIS SUPPLEMENTARY INFORMATION |
| | OR DOES IT REPLACE ANOTHER DETAIL? PLEASE INCORPORATE |
| | THIS DETAIL INTO THE PLAN IF IT SUPERSEDES ANOTHER |
| | DETAIL (OR OTHER DETAILS). |
| | |
| | 2. DETAIL PROVIDED SPECS "BRACKETS"; PLEASE PROVIDE A |
| | BASIC DESCRIPTION OF BRACKET. A DRAWING OF THE Z TYPE |
| | BRACKET WAS PROVIDED BUT NO INFORMATION REGARDING |
| | THICKNESS OR MATERIAL, ONLY DESCRIBED AS "BRACKETS |
| | SUPPLIED W/CHARGER," FBC16. |
| | |
| | 3. SECTIONS TYPICALLY CORRELATE WITH A PLAN. CONCRETE |
| | IS SHOWN, APPEARS TO BE A PLAN VIEW AND ELEVATION, BUT |
| | NOT MARKED AS SUCH (BOTH VIEWS LABELED TOGETHER AS |
| | SECTION A1). SOME OF THE DETAILS ON S1 ARE FOR WOOD |
| | SUBSTRATE, STEEL SUBSTRATE. DOES THIS APPLY TO CONCRETE |
| | SUBSTRATE ONLY? WHY ISN'T WOULDN'T THIS BE B1-1? SEE |
| | SHEET S1, PLAN SPECIFIES SOME (BUT NOT ALL) OF THE |
| | DETAILS ON THAT SHEET. FOR INSTANCE, SECTION A1.1 DOES |
| | NOT APPEAR ON THE KEY PLAN. DOES THAT MEAN THAT IT'S |
| | NOT BEING USED? ALSO, SHOULDN'T THE KEY PLAN BE REVISED |
| | TO INCORPORATE THE NEW DETAIL TO SHOW WHERE THIS DETAIL |
| | WILL BE IMPLEMENTED? FBC16, FBC*106. |
| | |
| | 4. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE ALL |
| | TITLE BLOCK INFORMATION REQUIRED FAC61G15-23.002 |
| | (WWW.FBPE.ORG, LAWS & RULES). |
| | |
| | 5. CALCULATIONS WERE SUPPLIED (AT TIME OF ORIGINAL |
| | PERMIT). IT APPEARS THAT CALCULATIONS WERE FOR WIND |
| | COLUMNS ONLY. PLEASE CONFIRM THAT THIS CHANGE OF |
| | SPECIFICATION DOES NOT AFFECT THE CALCULATIONS. IF THEY |
| | DO, PLEASE SUBMIT NEW CALCULATIONS FOR OUR RECORDS. |
| | |