| Plan Review Notes For Permit 09020366 |
| Permit Number |
09020366 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-27 14:43:05 | BATTERY CHARGING STATIONS ARE FOR FORKLIFTS AND | | | ELECTRIC PALLET JACKS. THE BATTERIES BEING CHARGED STAY | | | MOUNTED ON THE MACHINES (NOT STATIONARY) THEREFORE | | | ADDITIONAL VENTILATION IS NOT REQUIRED. |
|