| Plan Review Notes For Permit 09020353 |
| Permit Number |
09020353 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-18 09:53:16 | RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. | | | | | | 1- A) PROVIDE COMPLETE INSTALLATION SCHEDULE AS | | | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE | | | DEBRIS IMPACT PROTECTION. SEE ATTACHED COPY. | | | | | | B) CLEARLY MARK ON STORM PANELS SHUTTERS DRAWINGS | | | SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNT, BUILT | | | OUT, ETC. SEE SHEETS 2, 3 AND 4) AND SPECIFIC ANCHOR | | | TYPE AND SPACING TO BE USED ACCORDING TO THE DESIGN | | | PRESSURES, PANEL, SPAN, EDGE DISTANCE AND STRUCTURE TO | | | BE ATTACHED TO (EG: CONCRETE, CONCRETE BLOCK OR WOOD. | | | SEE SHEET 5). | | | | | | 2- SINGLE HUNG WINDOWS NOA 04-0504.05 SUBMITTED EXPIRED | | | ON JULY 11, 2007. NEED TO PROVIDE CURRENT PRODUCT | | | APPROVAL AS REQUIRED BY DCA RULE 9B-72. | | | | | | 3- PROVIDE TWO COPIES OF EACH PRODUCT APPROVAL. ONLY | | | ONE COPY SUBMITTED. | | | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTE. | | | | | | 5- A)SPECIFY SIZE OF WINDOW AND LOCATION (EG: BEDROOM, | | | ETC) TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS | | | OF SEC. 1025.2 FBC 2004. | | | | | | B) SPECIFY TYPE OF EXISTING WINDOW TO BE REPLACED. (EG; | | | SINGLE HUNG, CASEMENT, ETC) TO VERIFY COMPLIANCE WITH | | | EGRESS REQUIREMENTS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|