2009-02-18 09:53:16RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- A) PROVIDE COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION. SEE ATTACHED COPY.
  
 B) CLEARLY MARK ON STORM PANELS SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNT, BUILT
 OUT, ETC. SEE SHEETS 2, 3 AND 4) AND SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, PANEL, SPAN, EDGE DISTANCE AND STRUCTURE TO
 BE ATTACHED TO (EG: CONCRETE, CONCRETE BLOCK OR WOOD.
 SEE SHEET 5).
  
 2- SINGLE HUNG WINDOWS NOA 04-0504.05 SUBMITTED EXPIRED
 ON JULY 11, 2007. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72.
  
 3- PROVIDE TWO COPIES OF EACH PRODUCT APPROVAL. ONLY
 ONE COPY SUBMITTED.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 5- A)SPECIFY SIZE OF WINDOW AND LOCATION (EG: BEDROOM,
 ETC) TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. 1025.2 FBC 2004.
  
 B) SPECIFY TYPE OF EXISTING WINDOW TO BE REPLACED. (EG;
 SINGLE HUNG, CASEMENT, ETC) TO VERIFY COMPLIANCE WITH
 EGRESS REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER