2009-07-07 10:20:05 
  
 PERMIT # 09020319
 2201 45TH STREET
 COLUMBIA HOSPITAL/ 1ST FLOOR EMERGENCY DEPART
 ALTERATIONS
 2007 FBC
 07/07/09
  
 BUILDING PROVISO:
 SHEET A3.51
 1)ALTERNATE EFIS SYSTEM 08-0709.05 THIS PRODUCT
 APPROVAL WAS TESTED WITH
 PLYWOOD BACKING PROVIDING HIGHER PRESSURES. TYPE I,
 TYPE II BUILDINGS ARE NOT ALLOWED
 TO HAVE PLYWOOD SHEATHING UNLESS FIRE RESISTANT TREATED
 PLYWOOD WAS INSTALLED.SECTION
 603.1(1)(1.2). SHEET A3.51INDICATES 1/2 INCH SHEATHING
 IS TO BE INSTALLED OR DENSEGLASS GOLD.
 THIS PARTICULAR NOA WAS TESTED USING A 5/8 INCH
 EXTERIOR GRADE PLYWOOD, NOT 1/2 INCH.
  
 08-0709.05 ALTERNATE EFIS NOA TO BE SUBMITTED BEFORE
 INSPECTION.
  
 07-0108.01 EFIS NOA TO BE SUBMITTED BEFORE INSPECTION.
  
  
 2) WINDOW NOA 07-0817.04 TO BE SUBMITTED BEFORE
 INSPECTION.
  
 3) LINTEL PRODUCT APPROVAL TO BE SUBMITTED BEFORE
 INSPECTION.
  