| Plan Review Notes For Permit 09020319 |
| Permit Number |
09020319 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-07-07 10:20:05 | | | | | | | PERMIT # 09020319 | | | 2201 45TH STREET | | | COLUMBIA HOSPITAL/ 1ST FLOOR EMERGENCY DEPART | | | ALTERATIONS | | | 2007 FBC | | | 07/07/09 | | | | | | BUILDING PROVISO: | | | SHEET A3.51 | | | 1)ALTERNATE EFIS SYSTEM 08-0709.05 THIS PRODUCT | | | APPROVAL WAS TESTED WITH | | | PLYWOOD BACKING PROVIDING HIGHER PRESSURES. TYPE I, | | | TYPE II BUILDINGS ARE NOT ALLOWED | | | TO HAVE PLYWOOD SHEATHING UNLESS FIRE RESISTANT TREATED | | | PLYWOOD WAS INSTALLED.SECTION | | | 603.1(1)(1.2). SHEET A3.51INDICATES 1/2 INCH SHEATHING | | | IS TO BE INSTALLED OR DENSEGLASS GOLD. | | | THIS PARTICULAR NOA WAS TESTED USING A 5/8 INCH | | | EXTERIOR GRADE PLYWOOD, NOT 1/2 INCH. | | | | | | 08-0709.05 ALTERNATE EFIS NOA TO BE SUBMITTED BEFORE | | | INSPECTION. | | | | | | 07-0108.01 EFIS NOA TO BE SUBMITTED BEFORE INSPECTION. | | | | | | | | | 2) WINDOW NOA 07-0817.04 TO BE SUBMITTED BEFORE | | | INSPECTION. | | | | | | 3) LINTEL PRODUCT APPROVAL TO BE SUBMITTED BEFORE | | | INSPECTION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR | | | FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE PUBLIC | | | RECORD, AVAILABLE TO THE PUBLIC UPON | | | REQUEST. YOUR E-MAIL COMMUNICATIONS ARE THEREFORE | | | SUBJECT TO PUBLIC DISCLOSURE. |
|