Plan Review Notes
Plan Review Notes For Permit 09020319
Permit Number 09020319
Review Stop P
Sequence Number 2
Notes
Date Text
2009-06-12 16:03:07DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 NFPA 99C 2002
 CITY OF WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH
 HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL
 NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE
 III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO
 A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM
 OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA
 MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL.
 ****RESPONSE NOTED, BUT THE 2" HUB DRAIN CONNECTING TO
 THE STORM ABOVE THE CEILINGON SHT P1.01 IS NOT AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL BE DRAINED
 SEPARATELY FROM THE BUILDING AS INDICATED IN COMMENT. A
 RELIEF VENT, (GOOSENECK) IS REQUIRED ON THE CONDENSATE
 PIPING AS IT EXITS THE BUILDING IF THE CONDENSATE WILL
 BE CONNECTED TO THE STORM LINE OUTSIDE THE BUILDING.
 SECTION 314.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  