| 2009-06-12 16:03:07 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | NFPA 99C 2002 |
| | CITY OF WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH |
| | HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL |
| | NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE |
| | III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO |
| | A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM |
| | OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA |
| | MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL. |
| | ****RESPONSE NOTED, BUT THE 2" HUB DRAIN CONNECTING TO |
| | THE STORM ABOVE THE CEILINGON SHT P1.01 IS NOT AN |
| | APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL BE DRAINED |
| | SEPARATELY FROM THE BUILDING AS INDICATED IN COMMENT. A |
| | RELIEF VENT, (GOOSENECK) IS REQUIRED ON THE CONDENSATE |
| | PIPING AS IT EXITS THE BUILDING IF THE CONDENSATE WILL |
| | BE CONNECTED TO THE STORM LINE OUTSIDE THE BUILDING. |
| | SECTION 314.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |