| 2009-06-12 14:21:15 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. PLANS HAVE BEEN CHANGED TO SHOW THE CONDENSATE |
| | DISCHARGING INTO A FUNNEL INTO STORM WATER RISER. THIS |
| | IS NOT ACCEPTABLE AS THIS CREATES AN OPENING OF THE |
| | STORMWATER SYSTEM INTO THE BUILDING. IF THE STORMWATER |
| | DRAIN WERE TO BECOME OBSTRUCTED IT WOULD LEAD TO A |
| | BACKUP OF RAIN WATER INTO THE BUILDING. CONDENSATE |
| | SHALL DISCHARGE OUTDOORS AT AN APPROVED LOCATION OR TIE |
| | INTO STORMWATER OUTSIDE THE BUILDING. PLEASE CONTACT |
| | PLUMBING OR MECHANICAL REVIEWER TO DISCUSS OPTIONS. |
| | FBC-M 307.2.1. |
| | |
| | 2. PRODUCT APPROVAL SUBMITTED FOR FANS AND AHU. NO DATA |
| | PROVIDED FOR RTU. MAY BE A PROVISO ITEM ONCE ALL OTHER |
| | ISSUES ARE ADDRESSED. FBC-M 301.12. |
| | |
| | 3. PLAN SHOWS AUXILIARY DRAIN DISCHARGING ONTO ROOF. |
| | ROOFTOP UNITS NOT LIKELY DESIGNED WITH AUX. DRAIN |
| | OUTLET. ALSO, WOULD NOT BE DISCHARGING TO A CONSPICUOUS |
| | LOCATION AS REQUIRED BY FBC-M 307.2.3. ON DOWN-FLOW |
| | UNITS AND ALL OTHER COILS THAT DO NOT HAVE A SECONDARY |
| | DRAIN AND DO NOT HAVE A MEANS TO INSTALL AN AUXILIARY |
| | DRAIN PAN, A WATER-LEVEL MONITORING DEVICE SHALL BE |
| | INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS DEVICE |
| | SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT THAT |
| | THE PRIMARY DRAIN BECOMES RESTRICTED. EXTERNALLY |
| | INSTALLED DEVICES AND DEVICES INSTALLED IN THE DRAIN |
| | LINE SHALL NOT BE PERMITTED IN ACCORDANCE WITH FBC-M |
| | 307.2.3.1. |
| | |