2009-06-12 14:21:15REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. PLANS HAVE BEEN CHANGED TO SHOW THE CONDENSATE
 DISCHARGING INTO A FUNNEL INTO STORM WATER RISER. THIS
 IS NOT ACCEPTABLE AS THIS CREATES AN OPENING OF THE
 STORMWATER SYSTEM INTO THE BUILDING. IF THE STORMWATER
 DRAIN WERE TO BECOME OBSTRUCTED IT WOULD LEAD TO A
 BACKUP OF RAIN WATER INTO THE BUILDING. CONDENSATE
 SHALL DISCHARGE OUTDOORS AT AN APPROVED LOCATION OR TIE
 INTO STORMWATER OUTSIDE THE BUILDING. PLEASE CONTACT
 PLUMBING OR MECHANICAL REVIEWER TO DISCUSS OPTIONS.
 FBC-M 307.2.1.
  
 2. PRODUCT APPROVAL SUBMITTED FOR FANS AND AHU. NO DATA
 PROVIDED FOR RTU. MAY BE A PROVISO ITEM ONCE ALL OTHER
 ISSUES ARE ADDRESSED. FBC-M 301.12.
  
 3. PLAN SHOWS AUXILIARY DRAIN DISCHARGING ONTO ROOF.
 ROOFTOP UNITS NOT LIKELY DESIGNED WITH AUX. DRAIN
 OUTLET. ALSO, WOULD NOT BE DISCHARGING TO A CONSPICUOUS
 LOCATION AS REQUIRED BY FBC-M 307.2.3. ON DOWN-FLOW
 UNITS AND ALL OTHER COILS THAT DO NOT HAVE A SECONDARY
 DRAIN AND DO NOT HAVE A MEANS TO INSTALL AN AUXILIARY
 DRAIN PAN, A WATER-LEVEL MONITORING DEVICE SHALL BE
 INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS DEVICE
 SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT THAT
 THE PRIMARY DRAIN BECOMES RESTRICTED. EXTERNALLY
 INSTALLED DEVICES AND DEVICES INSTALLED IN THE DRAIN
 LINE SHALL NOT BE PERMITTED IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  