Plan Review Notes
Plan Review Notes For Permit 09020319
Permit Number 09020319
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-06-11 12:56:36COMMENTS FROM THE FIRST REVIEW APPEAR TO HAVE BEEN
 ADDRESSED AND THE PLANS HAVE BEEN APPROVED AND STAMPED.
 PLEASE SEE THE FOLLOWING:
  
 1) FIRE AND SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH UL 555 PRIOR TO FINAL INSPECTION.
  
 2) FIRE DEPARTMENT VALVES TO BE 2 1/2" CONNECTIONS TO 1
 1/2" REDUCER WITH CHAIN AND CAP.