| Plan Review Notes For Permit 09020319 |
| Permit Number |
09020319 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-06-11 12:56:36 | COMMENTS FROM THE FIRST REVIEW APPEAR TO HAVE BEEN | | | ADDRESSED AND THE PLANS HAVE BEEN APPROVED AND STAMPED. | | | PLEASE SEE THE FOLLOWING: | | | | | | 1) FIRE AND SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN | | | ACCORDANCE WITH UL 555 PRIOR TO FINAL INSPECTION. | | | | | | 2) FIRE DEPARTMENT VALVES TO BE 2 1/2" CONNECTIONS TO 1 | | | 1/2" REDUCER WITH CHAIN AND CAP. |
|