Date Text
2009-03-27 11:56:07DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 NFPA 99C 2002
 CITY OF WPB MUNICIPAL CODE
  
 1. SHT A0.00 CODE CRITERIA SHALL BE UPDATED TO FBC-2007
 W/2009 SUPPLEMENTS AS THE PERMIT WILL BE APPLIED FOR
 AFTER MARCH 1 2009. ALSO ADD NFPA 99C 2002 FOR THE
 MED-GAS CODE CRITERIA.
  
 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH
 HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL
 NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE
 III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO
 A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM
 OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA
 MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  