| 2009-03-27 11:56:07 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | NFPA 99C 2002 |
| | CITY OF WPB MUNICIPAL CODE |
| | |
| | 1. SHT A0.00 CODE CRITERIA SHALL BE UPDATED TO FBC-2007 |
| | W/2009 SUPPLEMENTS AS THE PERMIT WILL BE APPLIED FOR |
| | AFTER MARCH 1 2009. ALSO ADD NFPA 99C 2002 FOR THE |
| | MED-GAS CODE CRITERIA. |
| | |
| | 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH |
| | HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL |
| | NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE |
| | III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO |
| | A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM |
| | OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA |
| | MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |