| 2009-03-26 20:45:13 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING NOTES HAVE BEEN ADDED TO ONE SET OF |
| | SUBMITTED PLANS TO ASSIST IN MAKING CORRECTIONS. |
| | |
| | 1. PAGE M2.01 AND M4.03: PLANS SHOW CONDENSATE FROM FCU |
| | DISCHARGING INTO SANITARY SEWER VIA HUB DRAIN ABOVE |
| | CEILING. CONDENSATE SHALL NOT DISCHARGE INTO SANITARY |
| | SEWER SYSTEM IN ACCORDANCE WITH CITY ORDINANCE. |
| | CONDENSATE SHALL DISCHARGE INTO STORMWATER SYSTEM OR |
| | DIRECTLY TO THE OUTDOORS. SHOW CONDENSATE DISCHARGE |
| | LOCATION IN ACCORDANCE WITH FBC-M 307.2.1. |
| | |
| | 2. PAGES M4.02, M4.03 AND M4.04: ALL APPLIANCES, |
| | EQUIPMENT AND SUPPORTS WHICH ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. PROVIDE MANUFACTURER'S |
| | DATA FOR FANS AND ROOFTOP UNITS SHOWING THESE |
| | APPLIANCES ARE DESIGNED FOR WIND RESISTANCE. ALSO, SHOW |
| | HOW FANS, DUCTWORK AND SUPPORTS ARE TO BE SECURED TO |
| | STRUCTURE FOR WIND RESISTANCE. |
| | |
| | 3. PAGE M4.03: SHOW HOW FAN-COIL AND ROOFTOP UNITS ARE |
| | TO BE PROVIDED WITH AUXILIARY DRAIN PROTECTION IN |
| | ACCORDANCE WITH FBC-M 307.2.3. |
| | |
| | NOTE: THIS PLAN WAS SUBMITTED WITHOUT APPLICATION FOR |
| | PERMIT. THE 2007 FBC IS IN EFFECT AS OF MARCH 1, 2009. |
| | PLANS WILL REMAIN IN FAIL STAUS PENDING APPLICATION FOR |
| | PERMIT. |
| | |