| 2009-03-26 08:54:00 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: IT IS IMPORTANT TO KNOW THAT PLANS WERE ONLY |
| | SUBMITTED FOR PLAN REVIEW ONLY. THIS DOES NOT *LOCK* A |
| | PROJECT UNDER ANY SPECIFIC CODE EDITIONS UNLESS PERMIT |
| | APPLICATION IS MADE. AS THE PROJECT WAS ONLY SUBMITTED |
| | FOR PLAN REVIEW AND IS DESIGNED UNDER THE 2004 FBC AS |
| | OF MARCH 1, 2009 THE STATE OF FLORIDA UNDER FS 553.73 |
| | HAS ADOPTED THE 2007 FBC WITH 2009 REVISIONS. |
| | PLEASE ALSO KNOW SOME OTHER CODES SUCH AS THE LIFE |
| | SAFETY CODE AND STATE FIRE CODE WERE ALSO REVISED PER |
| | FLORIDA ADMINISTRATIVE CODE 69A-60.003 AND .004 BY THE |
| | STATE FIRE MARSHAL. |
| | THE FOLLOWING CODES NEED TO BE ON PLANS. PLEASE BE SURE |
| | THE FOLLOWING ARE ON ELECTRICAL AS WELL. SOME CODES |
| | STATED ON PLANS ARE OK AND IN EFFECT. PLEASE BE SURE |
| | THE FOLLOWING ARE UPDATED ON ALL RELEVANT SHEETS. |
| | |
| | 2007 FBC W/2009 REVISIONS. |
| | 2006 NFPA-101 |
| | 2006 NFPA-1 |
| | 2005 NFPA-70 (ALREADY ON COVER) |
| | 2002 NFPA-72 (ALREADY ON BOTH) |
| | 2002 NFPA-110 ( ALREADY ON BOTH) |
| | |
| | 2) NOTE: PLEASE SEE FAC 61G1-16.004 AND FLORIDA |
| | STATUTES 481.219 AS THE ARCHITECTURAL TITLE BLOCKS ARE |
| | MISSING REQUIRED INFORMATION AS WELL AS STATE REQUIRED |
| | LICENSING. |
| | MISSING PRINTED NAME OF ARCHITECT |
| | MISSING PRINTED LICENSE NUMBER OF ARCHITECT |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH |
| | 2009 GLITCH AMENDMENTS. THIS CHAPTER WAS COMPLETELY |
| | REVISED FROM THE FIRST PRINTING OF THE 2007 FBC. THERE |
| | ARE SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT. |
| | |
| | ** THERE ARE LOCATIONS WHICH REQUIRE AUTOMATED LIGHTING |
| | CONTROLS HOWEVER NOT SHOWN ON PLANS PER FBC |
| | 13-415.AB.1,.1.1,.1.2, .1.3. |
| | ONE EXAMPLE ONLY IS 1-125. THIS IS ONE LOCATION ONLY |
| | GIVEN AS A BENEFIT. PLEASE BE AWARE THERE ARE MANY |
| | OTHERS. |
| | |
| | ** PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2, 13-415.AB.5, 13-415.AB.5.1, 13-415.B |
| | |
| | 4) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION |
| | SYSTEM/ADDITION/REWORK WILL BE UNDER SEPARATE PERMIT |
| | AND PLANS. |
| | |
| | 5) NOTE: ALL WORKING CLEARANCE SHALL MEET 110.26. BASED |
| | ON THE NURSE STATION ELEVATION ALONE THERE ARE SEVERAL |
| | ITEMS WHICH REQUIRE CLEARANCE HOWEVER DO NOT MEET THE |
| | SECTIONS. |
| | |
| | 6) NOTE: PLEASE SEE 240.12,700.27, 701.18. PLEASE |
| | PROVIDE COMPLETE SELECTIVE COORDINATION FOR SYSTEMS |
| | INCLUDING NEW EQUIPMENT BEING INSTALLED. THIS STUDY |
| | NEEDS TO INCLUDE TIME CURVES. SOME INFORMATION SHOWN |
| | AND SUBMITTED HOWEVER BASED ON E7.01 NOT MATCHING RISER |
| | COMPLETELY AND NOT TIME CURVES SUBMITTED IT IS NOT |
| | KNOWN IF MINIMUM CODE COMPLIANCE IS MET. SEE COMMENT #8 |
| | ALSO. |
| | |
| | 7) NOTE: PLEASE SEE 517.17. PLEASE PROVIDE COMPLIANCE |
| | BY SHOWING THE PROTECTION OF SYSTEM. |
| | |
| | 8) NOTE: PLEASE GO THROUGH RISER, CONDUCTORS AND ALL |
| | OVER CURRENT PROTECTION DEVICES. THERE ARE ITEMS WHICH |
| | DO NOT COORDINATE. |
| | 215.5, 110.9, 240.4, 310.16, 240.12 ETC THESE CODE |
| | SECTIONS ARE GIVEN IN GENERAL AS COORDINATION OF |
| | CONDUCTORS, OVER CURRENT PROTECTION, PANELS ETC EFFECT |
| | ALL SECTIONS. |
| | |
| | FOR EXAMPLE: PLEASE SEE RISER LINE DIAGRAM, MAIN NDB |
| | INDICATES A NEW BREAKER TO FEED EDNH. THIS IS SHOWN |
| | WITH A 125AMP OCP ON THE LINE DIAGRAM YET THE |
| | COORDINATION STUDY RISER SHOWS THIS BEING A 300AMP |
| | BREAKER TO THE NEW 300AMP MLO. |
| | |
| | FOR EXAMPLE: THE RISER INDICATES THE PANEL BEING FED AS |
| | NOTED ABOVE AS EDNH, HOWEVER BASED ON THE PANEL |
| | DESIGNATION ON E7.03 THE PANEL IS MARKED AS EDHN. ONE |
| | COULD ASSUME THIS IS ONLY A MISPRINT HOWEVER ALL OF |
| | THESE ITEMS NEED TO COORDINATE. |
| | |
| | FOR EXAMPLE: THE LOAD IN EDHN/EDNH EXCEEDS THE 125AMP |
| | BREAKER FEEDING THIS PANEL BASED ON RISER. |
| | |
| | ** THESE ARE TWO EXAMPLES ONLY GIVEN AS A BENEFIT. |
| | THERE ARE OTHERS. |
| | |
| | 9) NOTE: PLEASE SHOW THE TRANSFORMER GROUNDING |
| | LOCATIONS. PLEASE INCLUDE ON RISER THE SIZE OF THE GEC |
| | AND CONNECTION POINT. |
| | 250.66,250.20,250.30. |
| | |
| | 10) NOTE: PLEASE SEE 408.4. THE PANEL SCHEDULES NEED TO |
| | BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | STATING, RECEPTACLES, OR CONSOLE OR OTHER GENERIC TERMS |
| | IS NOT PERMITTED. THESE NEED TO BE CLEAR TO THE ROOMS |
| | AND AREAS. FOR EXAMPLE: * RECEPTACLES RM 101, ETC. |
| | THESE MAY BE ALPHA OR NUMERIC DESIGNATIONS BASED ON |
| | PLANS. |
| | |
| | ** IMPORTANT: AS NOTED ABOVE THE PROJECT WAS NOT |
| | SUBMITTED FOR PERMIT UNDER THE 2004 FBC. PLEASE REVISE |
| | ALL DESIGNS |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |