| Date |
Text |
| 2009-03-16 15:50:54 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. THIS IS A PLAN CHECK ONLY. THIS REVIEW WILL REMAIN |
| | IN FAILED STATUS UNTIL PERMIT APPLICATION SUBMITTED. |
| | |
| | 2. GOVERNING CODE EFFECTIVE MARCH 1, 2009 IS FBC 2007 |
| | WITH 2009 SUPPLEMENTS, FS553. PLEASE REVISE. |
| | |
| | 3. PLEASE INDICATE WHICH METHOD OF COMPLIANCE UNDER |
| | WHICH THIS PROPOSED ALTERATION HAS BEEN DESIGNED, FBC |
| | EB 101.5. |
| | |
| | 4. FBC TABLE 601, SHEET A0.00, BUILDING TYPE 1A |
| | DECLARED, I2 OCCUPANCY. 3 HOUR FIRE RESISTANCE REQUIRED |
| | FOR TYPE 1A, I2 OCCUPANCY; 2 HOUR SPECIFIED ON PLAN |
| | (PLEASE NOTE THAT THE FOOTNOTE RE: 1 HOUR REDUCTION IS |
| | NOT APPLICABLE IN THIS CASE). |
| | |
| | 5. REVISE BUILDING INFORMATION TO INCLUDE BUILDING |
| | HEIGHT, FBC 6. |
| | |
| | 6. A0.0, UL ASSEMBLY DETAILS, SPECIFY FLOOR AND CEILING |
| | RUNNER TRACKS AND FASTENING, FBC706.5. |
| | |
| | 7. PROVIDE A HEAD OF WALL DETAIL, FBC706.5. |
| | |
| | 8. SHEET A0.01 IS NOT SEALED AND DATED, FS481. WHEN |
| | SUBMITTING FOR PERMIT, PLEASE CONFIRM THAT ALL SHEETS |
| | ARE SIGNED, SEALED, AND DATED. |
| | |
| | 9. ARCHITECT???S TITLE BLOCK TO BE IN COMPLIANCE WITH |
| | FAC61G1-16.004. |
| | |
| | 10. FBC1004.1.1, SHEET A0.10, PLEASE CLARIFY USE OF |
| | TREATMENT AREAS. OCCUPANT LOAD WAS DETERMINED BASED ON |
| | 240SF PER OCCUPANT; THIS IS THE MINIMUM FOR INPATIENT |
| | TREATMENT AREAS. ISN???T AN EMERGENCY ROOM AREA OFTEN |
| | AN OUTPATIENT TREATMENT AREA? PLEASE CLARIFY USE OF |
| | SPACE AND RATIONALE FOR USE OF 240SF FOR OCCUPANT LOAD. |
| | TABLE 1004.1.1 REQUIRES 100SF FOR OUTPATIENT. |
| | |
| | 11. FBC407.3, CORRIDOR WALLS SHALL BE CONSTRUCTED AS |
| | SMOKE PARTITIONS IN ACCORDANCE WITH FBC710. CORRIDORS |
| | 1-101, 1-105, ETC. DO NOT NOTE SMOKE PARTITION |
| | REQUIRED. THE WALL BETWEEN 1 208 AND CORRIDOR E 103 IS |
| | NOT NOTED AS A SMOKE PARTITION. PLEASE CLARIFY. |
| | |
| | 12. FBC407.2, EXAM 9 THROUGH 11 ARE OPEN TO CORRIDOR |
| | 1-105; IT IS NOT CLEAR WHICH EXCEPTION APPLIES, SEE |
| | FBC407.2.1(1). |
| | |
| | 13. MANEUVERING CLEARANCE, PULL SIDE FBC FIGURE 11-25 |
| | REQUIRED FOR ALL DOORS REQUIRED TO BE ACCESSIBLE. |
| | PLEASE NOTE DIMENSION TO SHOW COMPLIANCE: |
| | |
| | 1053, 1055, 1020, 1022 |
| | DOOR FROM ROOM 1-217 TO LAB, 1044, NOTED AS EXISTING |
| | |
| | PLEASE CHECK ALL AND CONFIRM COMPLIANCE FOR ALL DOORS |
| | IN THE RENOVATED AREA FBC11-4.1.6(1)(B). ONLY DOORS |
| | WHICH APPEAR NONCOMPLIANT ARE REFERENCED BUT OTHER |
| | DOORS MAY BE AFFECTED. |
| | |
| | 14. FBC407.2, CORRIDORS SHALL BE CONTINUOUS TO EXIT |
| | UNLESS ONE OF THE EXCEPTIONS NOTED. |
| | |
| | 15. A1.02, A NOTE STATES THAT TOILET ROOM WALLS WILL BE |
| | UPGRADED TO 2HR SMOKE/FIRE PARTITIONS. IT IS NOT CLEAR |
| | WHY THE SMOKE PARTITION IS NOT ALONG THE CORRIDOR WALL |
| | FBC407.2; PLEASE CLARIFY DESIGN INTENT. |
| | |
| | 16. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | FOR COMPONENTS & CLADDING; EIFS, WINDOWS. |
| | |
| | 17. A6 01 WINDOW A STATES THAT THIS WINDOW IS EXISTING |
| | (WITH AN EXPIRED NOA REFERENCE), SHEET A3.51 STATES |
| | THIS IS A NEW WINDOW, A1.02 STATES THIS IS NEW |
| | EXISTING. PLEASE CLARIFY SCOPE. |
| | |
| | 18. A1.02, I AM UNABLE TO LOCATE COILING SECURITY DOORS |
| | 1045 THROUGH 1050. MY APOLOGIES; PLEASE ADVISE. |
| | |
| | 19. FOR FIRE RATED WALLS, PLEASE NOTE METHOD OF |
| | COMPLIANCE FBC703.3. THE DETAILS DO NOT REFER TO AN |
| | ASSEMBLY NUMBER OR TIME FOR BUILDING ELEMENTS. |
| | |
| | 20. PLEASE NOTE CONCEALED SPACE SIGNAGE REQUIREMENT ON |
| | PLAN, FBC 419.3.9.7. |
| | |
| | 21. FBC407.2.2, NURSE???S AREA (AND SIMILAR SPACES) TO |
| | BE CONSTRUCTED AS REQUIRED FOR CORRIDORS. |
| | |
| | 22. FBC419.1.1, PLEASE SHOW COMPLIANCE WITH STATE |
| | REVIEW REQUIREMENTS (LETTER OR STAMPED PLAN). THIS ITEM |
| | MAY BE DONE PRIOR TO FIRST INSPECTION AS A REVISION, AT |
| | CONTRACTOR???S/OWNER???S RISK. |
| | |
| | 23. FBC11 4.13.7, DOORS AT ROOM 1 106, RECEPT/TRIAGE, |
| | REQUIREMENT FOR DOORS IN A SERIES. |
| | |