Plan Review Notes
Plan Review Notes For Permit 09020309
Permit Number 09020309
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-13 08:13:28BUILDING PLAN REVIEW
 PERMIT: 09020309
 ADD: 610 CLEMATIS STREET
 CONT: ARMENTI CONSTRUCTION INC.
 TEL: (561)641-9186
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 4) 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM
 OF THE BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR.
 2. WIND IMPORTANCE FACTOR, IW, AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 5) PROVIDE THE SHOP DRAWINGS OF THE GATES WITH CROSS
 SECTIONAL DIMENSION DETAILS SHOWING THE CLEAR HEIGHT
 AND WIDTH OF THE GATES AND WHAT MATERIALS ARE USE TO
 CONSTRUCT THEM AND HOW THEY ARE CONNECTED TO THE
 EXISTING STRUCTURE. ON SHEET A-1 ELEVATION 'A' SHOWS A
 4X4X1/4 STEEL FRAME/BEAM AT 8' WELDED TO TWO STEEL POST
 OF THE SAME SIZE, IS THE GATE CONNECTED TO HORIZONTAL
 FRAME/BEAM?
  
 6) THE CLAIM VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ELECTRICAL, STRUCTURAL, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT
 EXCLUDING LAND. OUR VALUATION REFERENCE IS ICC (BVD)
 MARSHALL SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3*
  
 7) 712.3.1 THROUGH PENETRATIONS OF
 FIRE-RESISTANCE-RATED WALLS SHALL COMPLY WITH SECTION
 712.3.1.1 OR 712.3.1.2. THROUGH PENETRATIONS SHALL BE
 PROTECTED BY AN APPROVED PENETRATION FIRE STOP SYSTEM
 INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL
 1479. ON SHEET A-1 STATE THE USE OF THE ROOM INTO WHICH
 THE NEW EMT CONDUIT IS ROUTED.
  
 8) SHEET A-2 SHOWS A 1' X 4" SPACE BETWEEN THE EXISTING
 STRUCTURE AND THE NEW POST, WILL THIS SPACE BE CLOSED
 OFF, AND IF SO, WHAT MATERIALS WILL BE USED. ADDITIONAL
 INFORMATION IS REQUIRED 106.1.2*
  
 9) THE ELEVATION DIMENSION DETAIL FOR THE CARD READERS
 AND INTERCOM SYSTEM IS NOT SHOWN ON THE PLANS, THESE
 SYSTEMS SHALL MEET THE REQUIREMENTS OF FBC 11-4.27.,
 THESE SYSTEMS SHALL MEET THE REQUIREMENTS OF FBC
 11-4.27.3
  
 10) THE GARRISON DESIGN GROUP IS MISSING THE CA NUMBER
 ON THE TITLE BLOCK. EITHER INDICATE THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON EACH SHEET OR REMOVE THE
 INFORMATION FROM THE DRAWINGS. THE TITLE BLOCK SHALL
 MEET THE FOLLOWING REQUIREMENTS. FAC 61G1-16.004 A
 TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
  
 11) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  