| 2009-03-13 08:13:28 | BUILDING PLAN REVIEW |
| | PERMIT: 09020309 |
| | ADD: 610 CLEMATIS STREET |
| | CONT: ARMENTI CONSTRUCTION INC. |
| | TEL: (561)641-9186 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH THE 2009 SUPPLEMENTS. |
| | |
| | 4) 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND |
| | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| | GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM |
| | OF THE BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR. |
| | 2. WIND IMPORTANCE FACTOR, IW, AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF TO BE USED FOR THE SELECTION OF |
| | EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 5) PROVIDE THE SHOP DRAWINGS OF THE GATES WITH CROSS |
| | SECTIONAL DIMENSION DETAILS SHOWING THE CLEAR HEIGHT |
| | AND WIDTH OF THE GATES AND WHAT MATERIALS ARE USE TO |
| | CONSTRUCT THEM AND HOW THEY ARE CONNECTED TO THE |
| | EXISTING STRUCTURE. ON SHEET A-1 ELEVATION 'A' SHOWS A |
| | 4X4X1/4 STEEL FRAME/BEAM AT 8' WELDED TO TWO STEEL POST |
| | OF THE SAME SIZE, IS THE GATE CONNECTED TO HORIZONTAL |
| | FRAME/BEAM? |
| | |
| | 6) THE CLAIM VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL THE TOTAL REPLACEMENT VALUE TO |
| | INCLUDE ELECTRICAL, STRUCTURAL, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT |
| | EXCLUDING LAND. OUR VALUATION REFERENCE IS ICC (BVD) |
| | MARSHALL SWIFT AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3* |
| | |
| | 7) 712.3.1 THROUGH PENETRATIONS OF |
| | FIRE-RESISTANCE-RATED WALLS SHALL COMPLY WITH SECTION |
| | 712.3.1.1 OR 712.3.1.2. THROUGH PENETRATIONS SHALL BE |
| | PROTECTED BY AN APPROVED PENETRATION FIRE STOP SYSTEM |
| | INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL |
| | 1479. ON SHEET A-1 STATE THE USE OF THE ROOM INTO WHICH |
| | THE NEW EMT CONDUIT IS ROUTED. |
| | |
| | 8) SHEET A-2 SHOWS A 1' X 4" SPACE BETWEEN THE EXISTING |
| | STRUCTURE AND THE NEW POST, WILL THIS SPACE BE CLOSED |
| | OFF, AND IF SO, WHAT MATERIALS WILL BE USED. ADDITIONAL |
| | INFORMATION IS REQUIRED 106.1.2* |
| | |
| | 9) THE ELEVATION DIMENSION DETAIL FOR THE CARD READERS |
| | AND INTERCOM SYSTEM IS NOT SHOWN ON THE PLANS, THESE |
| | SYSTEMS SHALL MEET THE REQUIREMENTS OF FBC 11-4.27., |
| | THESE SYSTEMS SHALL MEET THE REQUIREMENTS OF FBC |
| | 11-4.27.3 |
| | |
| | 10) THE GARRISON DESIGN GROUP IS MISSING THE CA NUMBER |
| | ON THE TITLE BLOCK. EITHER INDICATE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON EACH SHEET OR REMOVE THE |
| | INFORMATION FROM THE DRAWINGS. THE TITLE BLOCK SHALL |
| | MEET THE FOLLOWING REQUIREMENTS. FAC 61G1-16.004 A |
| | TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | |
| | 11) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561)805-6676 |
| | [email protected] |
| | |