| Plan Review Notes For Permit 09020303 |
| Permit Number |
09020303 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-18 10:56:12 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} SHEET D-1 SHOWS A JUNCTION BOX BEING REMOVED. THIS | | | IS IN THE AREA OF A REQUIRED LIGHTING OUTLET, SHOW | | | COMPLIANCE WITH NEC ARTICLE 210.70(A)(1) HABITABLE | | | ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING | | | OUTLET SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND | | | BATHROOM. | | | EXCEPTION NO. 1: IN OTHER THAN KITCHENS AND BATHROOMS, | | | ONE OR MORE RECEPTACLES CONTROLLED BY A WALL SWITCH | | | SHALL BE PERMITTED IN LIEU OF LIGHTING OUTLETS. | | | | | | 2} PROVIDE A LOAD CALCULATION PER 220.83 TO SHOW THE | | | EXISTING SERVICE RATING WILL SUPPORT THE NEW TANKLESS | | | SHOWN ON SHEET A-1. PROVIDE SPECIFICATIONS FOR THE | | | WATER HEATER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|