Plan Review Notes
Plan Review Notes For Permit 09020303
Permit Number 09020303
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-18 10:56:12 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET D-1 SHOWS A JUNCTION BOX BEING REMOVED. THIS
 IS IN THE AREA OF A REQUIRED LIGHTING OUTLET, SHOW
 COMPLIANCE WITH NEC ARTICLE 210.70(A)(1) HABITABLE
 ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND
 BATHROOM.
 EXCEPTION NO. 1: IN OTHER THAN KITCHENS AND BATHROOMS,
 ONE OR MORE RECEPTACLES CONTROLLED BY A WALL SWITCH
 SHALL BE PERMITTED IN LIEU OF LIGHTING OUTLETS.
  
 2} PROVIDE A LOAD CALCULATION PER 220.83 TO SHOW THE
 EXISTING SERVICE RATING WILL SUPPORT THE NEW TANKLESS
 SHOWN ON SHEET A-1. PROVIDE SPECIFICATIONS FOR THE
 WATER HEATER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  