Plan Review Notes
Plan Review Notes For Permit 09020294
Permit Number 09020294
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-26 11:03:00DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS IR1.3, IR1.4 & IR99.1 THE FOLLOWING INFORMATION
 IS MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHROIZATION),
 AND THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.306.
  
 2. SHTS A9.1 THRU A9.8 THE FOLLOWING INFORMATION IS
 MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(6) & FS 481.2055.
  
 3. SHT A9.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A
 SERVICE SINK ARE REQUIRED FOR THE "F" OCCUPANCY. PLEASE
 INDICATE THE LOCATION OF EACH REQUIRED FIXTURE.
  
 4. SHTS A9.1 & A9.2 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 ___FOR TOILET ROOM:
 A. 11-4.22.3 TURNING AREA
  
 5. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHTS M0.1 THRU M9.3 THE FOLLOWING INFORMATION IS
 MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G15-23.002(2) & FS 471.025.
  
 7. SHTS M9.2 & M9.3 INDICATES THE VENT FOR THE SANITARY
 PIPING AS A FRESH AIR INTAKE. THIS IS NOT CORRECT AS IT
 IS NOT A FRESH AIR INTAKE. PLEASE CLARIFY. SECTIONS
 106.1.1
  
 8. SHTS M9.2 PLUMBING PLAN & M9.3 SANITARY RISER
 DIAGRAM. THE VENT OFFSET BELOW THE FLOOR IS NOT
 APPROVED AT THE WATER CLOSET, NOR AT THE FLOOR DRAIN IN
 THE GENERATOR ROOM. SECTION 905.4. EVERY DRY VENT SHALL
 RISE VERTICALLY TO A MINIMUM OF 6 INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 SERVED.
  
 9. SUBMIT A SANITARY RISER DIAGRAM FOR THE FLOOR DRAINS
 IN THE GENERATOR ROOM AND THE PUMP ROOM. SHOW ALL PIPE
 SIZES, TRAPS AND VENTS. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved