| Date |
Text |
| 2009-02-26 11:03:00 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS IR1.3, IR1.4 & IR99.1 THE FOLLOWING INFORMATION |
| | IS MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE |
| | FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHROIZATION), |
| | AND THE PRINTED NAME OF THE PERSON SEALING THE |
| | DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.306. |
| | |
| | 2. SHTS A9.1 THRU A9.8 THE FOLLOWING INFORMATION IS |
| | MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE |
| | PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.004(6) & FS 481.2055. |
| | |
| | 3. SHT A9.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A |
| | SERVICE SINK ARE REQUIRED FOR THE "F" OCCUPANCY. PLEASE |
| | INDICATE THE LOCATION OF EACH REQUIRED FIXTURE. |
| | |
| | 4. SHTS A9.1 & A9.2 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ___LAV: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | ___FOR TOILET ROOM: |
| | A. 11-4.22.3 TURNING AREA |
| | |
| | 5. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 6. SHTS M0.1 THRU M9.3 THE FOLLOWING INFORMATION IS |
| | MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE |
| | PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING |
| | THE DOCUMENT. FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 7. SHTS M9.2 & M9.3 INDICATES THE VENT FOR THE SANITARY |
| | PIPING AS A FRESH AIR INTAKE. THIS IS NOT CORRECT AS IT |
| | IS NOT A FRESH AIR INTAKE. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 |
| | |
| | 8. SHTS M9.2 PLUMBING PLAN & M9.3 SANITARY RISER |
| | DIAGRAM. THE VENT OFFSET BELOW THE FLOOR IS NOT |
| | APPROVED AT THE WATER CLOSET, NOR AT THE FLOOR DRAIN IN |
| | THE GENERATOR ROOM. SECTION 905.4. EVERY DRY VENT SHALL |
| | RISE VERTICALLY TO A MINIMUM OF 6 INCHES ABOVE THE |
| | FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE |
| | SERVED. |
| | |
| | 9. SUBMIT A SANITARY RISER DIAGRAM FOR THE FLOOR DRAINS |
| | IN THE GENERATOR ROOM AND THE PUMP ROOM. SHOW ALL PIPE |
| | SIZES, TRAPS AND VENTS. SECTION 106.3.5.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |