| 2009-04-01 10:30:23 | *****DENIED***** |
| | |
| | |
| | 01. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 02. FIRE DEPARTMENT ACCESS ROADS SHALL BE DESIGNED AND |
| | MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE |
| | APPARATUS AND SHALL BE PROVIDED WITH AN ALL-WEATHER |
| | DRIVING SURFACE. |
| | |
| | 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 04. ON SHEET C91.6 INCLUDE IN NOTES AND/OR SHOW ON |
| | DIAGRAM THAT IN ADDITION TO THE ELECTRONIC SWITCH, THE |
| | OS&Y VALVE SHALL BE REQUIRED TO BE CHAINED AND LOCKED. |
| | |
| | 05. THE 2007 EDITION FLORIDA FIRE PREVENTION CODE |
| | (BASED ON NFPA 1- UNIFORM FIRE CODE - 2006 EDITION AND |
| | NFPA 101 - LIFE SAFETY CODE - 2006 EDITION) SHALL BE |
| | REFERENCED. |
| | |
| | 06. ON SHEET A9.0, THE DEAD END CORRIDOR IN A |
| | NON-SPRINKLERED BUILDING SHALL BE 20' INSTEAD OF 50' AS |
| | LISTED IN THE CODE REQUIREMENT SECTION. |
| | |
| | 07. ON SHEET A9.0, THE COMMON PATH REQUIREMENT FOR A |
| | NON-SPRINKLERED BUILDING SHALL BE 50' INSTEAD 100' AS |
| | LISTED IN THE CODE REQUIREMNT SECTION. |
| | |
| | 08. ON SHEET A9.0, REFERENCE IS MADE TO AUTOMATIC FIRE |
| | SPRINKLER SYSTEM - NOT REQUIRED - PER THE REQUIREMENT |
| | OF PBC AMENDMENT TO THE FLORIDA FIRE PREVENTION CODE |
| | 13.3.2.1.1.4; HAS THIS AMENDMENT BEEN ADOPTED BY THE |
| | JURISDICTION OF THE CITY OF WEST PALM BEACH? |
| | |
| | 09. ON SHEET A9.0, ELIMINATE/AMEND NOTE #9 UNDER |
| | APPLICABLE CODES. |
| | |
| | 10. IF ANY, WHAT TYPE OF CHEMICALS WILL BE STORED AT |
| | THE FACILITY AND IN WHAT QUANTITIES? |
| | |
| | 11. WILL THERE BE ANY MARKING, IDENTIFICATION, |
| | PLACARDING, ETC TO BE UTILIZED AT THE FACILITY? AND IF |
| | SO, PLEASE SHOW ON THE APPROPIATE PLAN SHEET. |
| | |
| | 12. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE EXTERIOR ELEVATION FRONTING OR FACING THE |
| | STREET OR PRINCIPAL VEHICULAR ACCESS TO THE PREMISES. |
| | AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH/STROKE. |
| | |
| | 13. ON SHEET F0.1 UPDATE REFERENCES TO NFPA 101 TO THE |
| | 2006 EDITION AND ELIMINATE REFERERENCE(S) TO PALM BEACH |
| | COUNTY CODES. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A |
| | RESPONSE LETTER INDICATING HOW/WHERE ON THE APPROPIATE |
| | PLAN SHEET EACH COMMENT WERE ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A.WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |