Plan Review Notes
Plan Review Notes For Permit 09020294
Permit Number 09020294
Review Stop E
Sequence Number 1
Notes
Date Text
2009-03-03 08:56:57** DENIED REVIEW **
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW
 UNDER THE 2004 CODE AND OTHER ADOPTED STANDARDS. THERE
 WILL BE A CODE CHANGE AS OF MARCH 1ST, 2009 WHICH WILL
 REQUIRE ALL PLANS TO BE REVISED TO THE NEW CODES.
 PLEASE BE AWARE THE SUBMISSION OF PLANS FOR PLAN REVIEW
 ONLY DOES NOT LOCK THE PROJECT IN UNDER THE CURRENT
 CODES IN EFFECT. ONLY PERMIT APPLICATIONS UNDER A
 LICENSED CONTRACTOR WITH REQUIRED MINIMUM FEES APPLIED
 FOR BEFORE THAT DATE WILL *LOCK* THE PROJECT UNDER THE
 CURRENT CODE EDITIONS. THIS WILL AFFECT THE DESIGNS ON
 THE PROJECT FOR MANY ASPECTS HOWEVER THE ELECTRICAL
 CODE IS NOT SCHEDULED TO BE CHANGED UNTIL JULY 1ST,
 2009.
  
 ** ANY REFERENCES BELOW TO FBC CHAPTER 1 IS BASED ON
 AMENDMENTS AS ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON THE PLANS. THE PLANS MUST LIST THE ACTUAL DESIGN
 DOCUMENTS.
 THERE ARE SEVERAL SHEETS WITH REFERENCES TO CODES WHICH
 ARE NO LONGER IN EFFECT.
 FOR EXAMPLE: THE STATE FAC RULE 69A-60.003 AND .004
 ADOPTED THE 2006 NFPA-1 AND 2006 NFPA-101 BEFORE THE
 ACTUAL ADOPTION OF THE NEW CODES. THE PLANS FOR EXAMPLE
 ON SHEET A9.0 DOES LIST THE PREVIOUS CODES AS WELL THE
 PREVIOUS ADOPTED RULE WHICH NO LONGER CONTAINS THESE
 CODES REFERENCES. IF THE FAC RULE IS GOING TO BE PLACED
 ON PLANS PLEASE REVISE TO THE SECTIONS AS NOTED ABOVE.
 PLEASE ALSO SEE OTHER EXAMPLES SUCH AS REFERENCE TO THE
 2002 NFPA-70 ( NATIONAL ELECTRICAL CODE). THE FOLLOWING
 CODES WILL BE STATED AND NEEDED ON BOTH THE
 ARCHITECTURAL COVER SHEET AND ELECTRICAL PLANS. IT IS
 NOTICED THAT SOME CODES ARE OK ON ELECTRICAL PLANS
 HOWEVER NOT ALL.
 PLEASE BE AWARE THAT SHEETS SUCH AS FIRE ALARM AND
 STRUCTURAL SHEETS MAY NEED TO BE REVISED FOR CURRENT
 CODES.
 *** KEEP IN MIND IF THIS PROJECT HAS NOT APPLIED FOR
 PERMIT BEFORE THE MARCH 1ST, 2009 DEADLINE ALL CODES
 STATED BELOW MAY NOT BE ACCURATE.
 *** MANY SHEETS IN THE SETS OF PLANS SUBMITTED ALSO
 STATE * PALM BEACH COUNTY* AS THE AMENDED LOCAL
 AUTHORITY. AS THIS PROJECT IS IN THE CITY OF WEST PALM
 BEACH PLEASE ADJUST NOTES ACCORDINGLY. THIS IS STATED
 ON NUMEROUS SHEETS AND PLANS.
 PLEASE LIST AS FOLLOWS BASED ON CURRENT CODES. IF
 APPLICATION IS NOT MADE SOME OTHER CODES WILL CHANGE.
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
 2006 NFPA-1
 2002 NFPA-72
  
 ** NOTES UPDATED: AS PERMIT HAS NOT BEEN APPLIED FOR
 BEFORE MARCH 1ST, THE NEW CODES SHALL BE BASED ON THE
 2007 FBC.
  
  
 3) NOTE: IN THE SET OF PLANS REVIEWED THERE ARE SEVERAL
 SHEETS WHICH WERE SIGNED AND DATED HOWEVER THEY ARE
 MISSING THE REQUIRED RAISED SEAL PER FS 471.025 AND FAC
 61G15-23.002.
 MANY OF THESE SHEETS ARE NOT ELECTRICAL IN NATURE
 HOWEVER THIS IS GIVEN AS A BENEFIT FOR INFORMATION.
 SHEETS: CU1.1,1.3,1.4,1.5 , CP 1.1,1.2, 1.4 AND 1.6
 THROUGH C9.18.
 THIS IS NOTED FOR DESIGN TEAM ONLY BY THIS REVIEWER. IF
 COMMENT IS NOT MADE BY OTHER TRADE(S) THIS IS STILL
 REQUIRED.
 FS 481.221, 471.025
  
 4) NOTE: ANY * LOCK OFF* TYPE OF BREAKERS ON THIS
 PROJECT SHALL HAVE THE LOCK OFF DEVICE BE AN INTEGRAL
 PART OF THE BREAKER. MOST OF THE CLIP ON OR SNAP ON
 TYPE DEVICES ARE NOT LISTED FOR PERMANENT INSTALLATION.
 PLEASE MAKE NOTE ON PLANS FOR THE TYPE OF BREAKERS
 REQUIRED. THE DIVISION SPECIFICATIONS WERE NOT CLEAR TO
 THE ACTUAL TYPE OF DEVICE INTENDED.
 110.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 5) NOTE: THE RISER CLEARLY INDICATES A CONNECTION OF A
 PORTABLE GENERATOR WITHOUT ANY FAIL SAFE OPERATION OF A
 TRANSFER SWITCH OF DEVICE OF SOME SORT. THIS
 INSTALLATION DOES NOT MEET 702.6. THE PROPOSED KIRK KEY
 INTERLOCK IS NOT A LISTED TRANSFER SWITCH OR DEVICE. IT
 ALSO DOES NOT PROVIDE FAIL SAFE OPERATION. PLEASE BE
 AWARE THAT INSTALLATION OF THIS TYPE OF DEVICE MAY ALSO
 VOID LISTING AND OR WARRANTY OF EQUIPMENT.
 110.3
 THIS COMMENT IS WITH RESPECT TO ALL PANELS AND ALL
 EQUIPMENT ON RISER WHICH INDICATE THIS SAME KIRK KEY
 INTERLOCK SYSTEM.
 THE INSTALLATION OF A PORTABLE GENERATOR WITH OUT THE
 USE OF TRANSFER EQUIPMENT MAY BE PART OF THE EXCEPTION.
 PLEASE PROVIDE AN ORIGINAL NOTARIZED LETTER FROM THE
 RESPONSIBLE AUTHORITY WHICH STATES THIS ENTIRE SCOPE OF
 WORK WILL ONLY BE DONE BY *QUALIFIED PERSONNEL* PER THE
 DEFINITIONS IN THE NATIONAL ELECTRICAL CODE ARTICLE
 100. THIS DOES NOT NEGATE THE FIRST PART OF THIS NOTE
 WITH RESPECT TO THE KIRK KEY BEING LISTED OR VOID
 LISTING OF EQUIPMENT.
 SEE OTHER NOTES BELOW WITH RESPECT TO ARC FLASH AND
 OTHER HAZARDS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION ON THE REQUIRED
 GROUND FAULT PROTECTION OF MAINS PER 240.13 AND 230.95.
  
 7) NOTE: PLEASE ALSO PROVIDE NOTES OR INFORMATION ON
 ALL MAINS. THE RISER LENDS TO THE FACT BOTH OF THESE
 ARE SHUNT TRIP HOWEVER DO BOTH OF THESE STILL CONTAIN
 THE REQUIRED MANUAL MEANS OF DISCONNECT RATED FOR THE
 LOAD SERVED PER 230.76 AND 230.79?
 IF ACTUAL LISTING IS PROVIDED THIS MAY ALSO HELP ANSWER
 QUESTION.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON TRANSFORMERS AS
 THE OVER CURRENT PROTECTION IS EXCEEDING THE MAXIMUM
 125% BASED ON 450.3.
 IF MEETING NOTES IN TABLES, TYPE OF UNIT NEEDS TO BE
 VERIFIED AND STATED ON PLANS. IF NOT MEETING NOTES ON
 TABLE 450.3 THE MAXIMUM OVER CURRENT PROTECTION SHALL
 BE 125%.
  
 9) NOTE: PLEASE VERIFY ALL TRANSFORMER LOCATIONS FOR
 LENGTH OF TAPPED CONDUCTORS PER 240.21. THE TAP RULES
 ARE BASED ON THE LENGTH OF CONDUCTORS AND AS SOME SEEM
 TO PERHAPS BE LOCATED SO THE LENGTHS ARE OVER THE
 ALLOWANCES IN THE SECTION NOTED, THIS NEEDS TO BE
 VERIFIED AT THIS TIME.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2009-02-25 16:54:43REVIEW HAS COMMENCED. ONCE REVIEW IS COMPLETED REVIEW
 WILL PROCEED INTO A FAILED STATUS.
 REVIEW WILL CONTINUE ON 3/2