| 2009-03-11 10:06:12 | BUILDING PLAN REVIEW |
| | PERMIT: 09020294 |
| | ADD: 4325 N HAVERHILL RD. |
| | CONT: MAJOR WORKING DRAWING REVIEW |
| | TEL: (561)632-5317 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOROR |
| | RESIDENT INSPECTOR, THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | NOTE: PLANS THAT ARE SUBMITTED FIRST TIME UNDER A |
| | PERMIT APPLICATION STARTING MARCH 1, 2009 WILL BE |
| | REVIEWED TO THE 2007 FBC, WITH THE 2009 SUPPLEMENTS |
| | THIS START DATE IS A MANDATED IMPLEMENTION DATE STATE |
| | WIDE. |
| | SINCE TO DATE NO CONTRACTOR HAS MADE APPLICATION TO |
| | CHANGE THIS MAJOR WORKING DRAWING REVIEW INTO A PERMIT |
| | APPLICATION THIS REVIEW WILL BE COMPLETED UNDER THE |
| | 2007FBC WITH 2009 SUPPLEMENTS, PLEASE UPDATE ALL PLANS |
| | TO REFECT AS SUCH!. SHEET A9.0 & S0.1. |
| | |
| | 2) SHEET A9.0 INDICATES FIRE SPRINKLERS NOT REQUIRED |
| | AND NOTED PER THE REQUIREMENT OF PBC AMENDMENT TO THE |
| | FIRE PREVENTION CODE SECTION 13.3.2.1.1.4. THIS |
| | FACILITY IS LOCATED WITHIN THE |
| | CITY OF WEST PALM BEACH, NOT THE COUNTY. ALSO NOTE |
| | SINCE THE 2004 FBC THERE ARE NO LONGER LOCAL AMENDMENT |
| | TO THE FBC EXCEPT FOR CHAPTER 1. |
| | |
| | 3) SHEET A9.0 WILL NEED TO PROVIDE THE TYPES OF |
| | MATERIALS TO BE STORED AND THE AMOUNTS TO DETERMINE THE |
| | TYPE OF OCCUPANCY. WITHOUT THIS INFORMATION WE CAN NOT |
| | CLASSIFY THIS BUILDING.THE PLANS INDICATE STORAGE OF |
| | SODIUM HYPOCHLORITE. SECTION 307.2 UNDER THE DEFINITION |
| | OF OXIDIZER THERE ARE FOUR CLASSIFICATIONS. PLEASE |
| | IDENTIFY WHICH OF THESE CATEGORIES WE WILL BE DEALING |
| | WITH AND THE AMOUNT TO BE STORED, STATE OF COMPOUND |
| | (GAS, LIQUID OR SOLID) AND WHAT TYPE OF STORAGE |
| | CONTAINER. ALSO PROVIDE THE MSDS SHEETS FOR THIS |
| | COMPOUND AND OTHER CHEMICALS TO BE STORED WITHIN THIS |
| | BUILDING. |
| | |
| | 4) THE COVERSHEET C1.1 INDICATES THE USE OF A 3MG |
| | CHLORINE CONTACT STORAGE TANK, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION, IS THIS 3 MILLION GALLONS OF |
| | CHLORINE, OR A MIXING TANK? IS THIS NEW CONSTRUCTION OR |
| | JUST A TIE IN ASA INDICATED ON SHEET S99.1. |
| | |
| | 5) SHEET A9.0 INDICATES THIS BUILDING TO BE A TYPE II-B |
| | CONSTRUCTION. WEST PALM BEACH ADMINISTRATIVE CODE |
| | 109.3.7 (1) FOR BUILDINGS OF TYPE I OR II CONSTRUCTION |
| | SHALL REQUIRE A RESIDENT INSPECTOR . A COPY OF THE |
| | PAPERWORK SHALL BE ATTACHED. |
| | |
| | 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 7A) EXTERIOR METAL DOORS SINGLE & DOUBLE DOORS |
| | 7B) WALL LOUVERS |
| | 7C) ROOFING ASSEMBLIES INCLUDING INSULATION |
| | 7D) ROLL UP DOOR |
| | |
| | 8) NO ENERGY CALCULATIONS WERE SUBMITTED, SHALL COMPLY |
| | WITH 13-101.1.1. METHOD A,B OR C. PLEASE PROVIDE THE |
| | INPUT DATA REPORT WITH THE ENRGY CALCULATIONS, PLEASE |
| | NOTE THE 2007 BUILDING CODE HAS UPDATED CHAPTER 13 BUT |
| | THE 2009 SUPPLEMENTS ARE NOT AVAILABLE AS OF YET. |
| | |
| | 9) NOTE THAT SHEET A9.7 DETAIL 04 ROOF INSULATION THIS |
| | AREA BY THE SCUPPER IS THE LOWEST LEVEL OF ROOF |
| | INSULATION AND THIS AREA WOULD NEED TO MEET AS THE |
| | MINIMUM R-VALUE LISSTED IN THE INPUT DATA REPORT. |
| | 13-404.ABC.1. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |