Plan Review Notes
Plan Review Notes For Permit 09020294
Permit Number 09020294
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-11 10:06:12BUILDING PLAN REVIEW
 PERMIT: 09020294
 ADD: 4325 N HAVERHILL RD.
 CONT: MAJOR WORKING DRAWING REVIEW
 TEL: (561)632-5317
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOROR
 RESIDENT INSPECTOR, THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
 NOTE: PLANS THAT ARE SUBMITTED FIRST TIME UNDER A
 PERMIT APPLICATION STARTING MARCH 1, 2009 WILL BE
 REVIEWED TO THE 2007 FBC, WITH THE 2009 SUPPLEMENTS
 THIS START DATE IS A MANDATED IMPLEMENTION DATE STATE
 WIDE.
 SINCE TO DATE NO CONTRACTOR HAS MADE APPLICATION TO
 CHANGE THIS MAJOR WORKING DRAWING REVIEW INTO A PERMIT
 APPLICATION THIS REVIEW WILL BE COMPLETED UNDER THE
 2007FBC WITH 2009 SUPPLEMENTS, PLEASE UPDATE ALL PLANS
 TO REFECT AS SUCH!. SHEET A9.0 & S0.1.
  
 2) SHEET A9.0 INDICATES FIRE SPRINKLERS NOT REQUIRED
 AND NOTED PER THE REQUIREMENT OF PBC AMENDMENT TO THE
 FIRE PREVENTION CODE SECTION 13.3.2.1.1.4. THIS
 FACILITY IS LOCATED WITHIN THE
 CITY OF WEST PALM BEACH, NOT THE COUNTY. ALSO NOTE
 SINCE THE 2004 FBC THERE ARE NO LONGER LOCAL AMENDMENT
 TO THE FBC EXCEPT FOR CHAPTER 1.
  
 3) SHEET A9.0 WILL NEED TO PROVIDE THE TYPES OF
 MATERIALS TO BE STORED AND THE AMOUNTS TO DETERMINE THE
 TYPE OF OCCUPANCY. WITHOUT THIS INFORMATION WE CAN NOT
 CLASSIFY THIS BUILDING.THE PLANS INDICATE STORAGE OF
 SODIUM HYPOCHLORITE. SECTION 307.2 UNDER THE DEFINITION
 OF OXIDIZER THERE ARE FOUR CLASSIFICATIONS. PLEASE
 IDENTIFY WHICH OF THESE CATEGORIES WE WILL BE DEALING
 WITH AND THE AMOUNT TO BE STORED, STATE OF COMPOUND
 (GAS, LIQUID OR SOLID) AND WHAT TYPE OF STORAGE
 CONTAINER. ALSO PROVIDE THE MSDS SHEETS FOR THIS
 COMPOUND AND OTHER CHEMICALS TO BE STORED WITHIN THIS
 BUILDING.
  
 4) THE COVERSHEET C1.1 INDICATES THE USE OF A 3MG
 CHLORINE CONTACT STORAGE TANK, PLEASE PROVIDE
 ADDITIONAL INFORMATION, IS THIS 3 MILLION GALLONS OF
 CHLORINE, OR A MIXING TANK? IS THIS NEW CONSTRUCTION OR
 JUST A TIE IN ASA INDICATED ON SHEET S99.1.
  
 5) SHEET A9.0 INDICATES THIS BUILDING TO BE A TYPE II-B
 CONSTRUCTION. WEST PALM BEACH ADMINISTRATIVE CODE
 109.3.7 (1) FOR BUILDINGS OF TYPE I OR II CONSTRUCTION
 SHALL REQUIRE A RESIDENT INSPECTOR . A COPY OF THE
 PAPERWORK SHALL BE ATTACHED.
  
 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 7A) EXTERIOR METAL DOORS SINGLE & DOUBLE DOORS
 7B) WALL LOUVERS
 7C) ROOFING ASSEMBLIES INCLUDING INSULATION
 7D) ROLL UP DOOR
  
 8) NO ENERGY CALCULATIONS WERE SUBMITTED, SHALL COMPLY
 WITH 13-101.1.1. METHOD A,B OR C. PLEASE PROVIDE THE
 INPUT DATA REPORT WITH THE ENRGY CALCULATIONS, PLEASE
 NOTE THE 2007 BUILDING CODE HAS UPDATED CHAPTER 13 BUT
 THE 2009 SUPPLEMENTS ARE NOT AVAILABLE AS OF YET.
  
 9) NOTE THAT SHEET A9.7 DETAIL 04 ROOF INSULATION THIS
 AREA BY THE SCUPPER IS THE LOWEST LEVEL OF ROOF
 INSULATION AND THIS AREA WOULD NEED TO MEET AS THE
 MINIMUM R-VALUE LISSTED IN THE INPUT DATA REPORT.
 13-404.ABC.1.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.