| 2009-05-29 16:18:12 | *** DENIED 2ND REVIEW **** |
| | |
| | ** SOME OF THE EXACT SAME NOTES FROM PREVIOUS REVIEW |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM |
| | BUILDING REVIEWER ALSO. THE ENGINEERING LETTER ATTACHED |
| | TO PLANS FROM IETS DOES NOT CONTAIN AN ORIGINAL |
| | SIGNATURE. IT IS IN FACT A RUBBER STAMP SIGNATURE. THIS |
| | IS NOT PERMITTED UNDER FS 471.025. THIS CAN BE |
| | CONFIRMED WITH THE FLORIDA BOARD OF ENGINEERS. THIS WAS |
| | NOTED EXACTLY AS PER PREVIOUS REVIEW YET THE SAME |
| | LETTER WITH THE SAME RUBBER STAMP ON EACH WAS SUBMITTED |
| | BACK. |
| | ORIGINAL SIGNATURE IS REQUIRED, FAC 61G15-23.002, |
| | FS471.025 |
| | |
| | 2) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM |
| | BUILDING REVIEWER. THE DOCUMENTS ATTACHED FOR |
| | ENGINEERED ENDEAVORS INC ARE SEALED WITH A RAISED SEAL |
| | WHICH IS NO LONGER IN USE IN THE STATE OF FLORIDA. THE |
| | SAID SEAL FOR MR. MICHAEL MOREL HAS NOT BEEN VALID FOR |
| | SEVERAL YEARS. FAC 61G15-23.002 RULING WAS REVISED IN |
| | FEBRUARY OF 2004 WHICH REQUIRED THE SEAL TO BE REVISED |
| | TO CONTAIN THE WORDING OF LICENSE INSTEAD OF |
| | *CERTIFICATE*. AN EXTENSION WAS GIVEN TO DECEMBER 31ST, |
| | 2005 HOWEVER ALL OLD SEALS AFTER SUCH DATE WERE NO |
| | LONGER PERMITTED TO BE USED IN THE STATE OF FLORIDA. |
| | NEW SEAL NEEDS TO BE OBTAINED. |
| | ** THIS IS ONLY NOTED BY THIS REVIEWER TO GIVE |
| | INFORMATION AHEAD OF TIME. THIS MAY HELP TO ALLEVIATE |
| | FURTHER DELAYS. |
| | |
| | 3) NOTE: AS NOTED ON PREVIOUS REVIEW. THE SEAL ON THE |
| | ELECTRICAL PLANS ARE NOT CLEAR AND VISIBLE. EVEN USE OF |
| | LEAD RUB DOES NOT IDENTIFY THE REQUIRED INFORMATION ON |
| | SAID SEAL. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002, .001 AND FLORIDA STATUTES 471.025. ALL |
| | INFORMATION ON SEALS NEEDS TO BE CLEAR AND VISIBLE. |
| | **ENGINEER MAY RE-SEAL PLANS, SIGN AND DATE IN THIS |
| | OFFICE IF THIS WOULD HELP WITH THE PROJECT. THE SEAL |
| | MUST HAVE ALL INFORMATION CLEAR AND VISIBLE. OBTAIN NEW |
| | SEAL IF IT CAN BE READ. |
| | |
| | 4) NOTE: THIS WAS NOTED ON PREVIOUS REVIEW. THERE ARE |
| | NOW TWO TRANSFER SWITCHES SHOWN ON PLANS. PLEASE SUBMIT |
| | THE MANUFACTURES SPECS/CUT SHEETS FOR ANY PROPOSED |
| | TRANSFER SWITCH AUTOMATIC, MANUAL, LEGALLY REQUIRED OR |
| | OPTIONAL STAND-BY. |
| | 90.7, 110.3, 701.7, 702.6. NO REVIEW CAN BE DONE AT |
| | THIS TIME FOR THSE ITEMS. |
| | ** THE GENERATOR SPECS/CUT SHEETS ARE THE ONLY RELEVANT |
| | SPECS IN SETS. (ATTACHED TO FRONT) |
| | |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |