| 2009-03-18 12:04:31 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. -- THE ISOMETRIC AS SHOWN DOES NOT SHOW |
| | ANY PIPING UNDERGROUND. THE PIPING TO THE METER AND OUT |
| | OF THE METER DOES NOT DROP DOWN FROM THE METER NOR DOES |
| | IT RISE UP TO THE METER ON THE SUPPLY SIDE. PLEASE |
| | CLARIFY. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. -- NOTE ON SHT 1 |
| | OF 1 NG GENERATOR INSTALLATION STATES, "3/4" BLACK IRON |
| | PIPE SUITABLE FOR NATURAL GAS ABOVE GROUND TO BE ROUTED |
| | TO 3/4" POLYETHELENE FROM THE TANK TO THE GENERATOR |
| | WITH A MINIMU 12-INCHES OF COVER". PLEASE INDICATE WHAT |
| | TANK. PLEASE SEE COMMENT #1 AS THE ISOMETRIC DOES NOT |
| | SHOW THE PIPING UNDERGROUND, OR IF PIPING IS SHOWN |
| | UNDERGROUND, THEN THE METER IS INDICATED BELOW GROUND. |
| | PLEASE CLARIFY. |
| | |
| | 3. ALL SHEETS, THE PROJECT DATA SHALL INCLUDE THE |
| | FBC-2004 WITH 2007 SUPPLEMENTS. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |