| Date |
Text |
| 2009-03-16 09:37:46 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: ENGINEERING LETTER ATTACHED TO PLANS FROM IETS |
| | DOES NOT CONTAIN AN ORIGINAL SIGNATURE. IT IS IN FACT A |
| | RUBBER STAMP SIGNATURE. THIS IS NOT PERMITTED UNDER FS |
| | 471.025. THIS CAN BE CONFIRMED WITH THE FLORIDA BOARD |
| | OF ENGINEERS. |
| | PLEASE USE ORIGINAL SIGNATURES EVEN IF COMMENT IS NOT |
| | MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE PROVIDE COMPLETE DOCUMENTATION ON THE |
| | TYPE OF GENERATOR SYSTEM BEING INSTALLED. IS THIS A |
| | LEGALLY REQUIRED SYSTEM? PLEASE SEE 701.11B3. ON SITE |
| | FUEL IS REQUIRED MEETING MINIMUM TIMES. |
| | PLEASE SEE FEDERAL CODE OF REGULATIONS TITLE 47 PART 12 |
| | FOR UPDATES OF SYSTEMS FOR CELL TOWER POWER BACK UP. |
| | THIS INCLUDES ANY 911 OR E911 SYSTEMS. |
| | SHEET 4 OF THE SET MENTIONS POSSIBLE BATTERY CABINETS |
| | HOWEVER THIS WAS NOT LOCATED ON ELECTRICAL SHEETS. ARE |
| | THERE BATTERY CABINETS PROVIDING 8HRS BACK UP AND THE |
| | GENERATOR IS IN ADDITION TO THIS? IS THERE NOT GOING TO |
| | BE ANY GENERATOR AND ONLY BATTERY? SEE NOTE #4 BELOW. |
| | |
| | 3) NOTE: THE FOLLOWING CODES NEED TO BE STATED ON |
| | ELECTRICAL PLANS. |
| | 2005 NFPA-70. |
| | |
| | 4) NOTE: THERE IS CONFUSION OVER WHAT SCOPE OF WORK IS |
| | BEING APPLIED FOR: THE PERMIT APPLICATION MENTIONS THE |
| | INSTALLATION OF A PERMANENT GENERATOR, ALONG WITH |
| | ATTACHED SPECS/CUT SHEETS, AND THE GAS PLAN. HOWEVER |
| | THE ELECTRICAL PLANS INDICATES A MANUAL TRANSFER SWITCH |
| | WITH A RECEPTACLE FOR A PORTABLE GENERATOR. THE |
| | ELECTRICAL RISER INDICATES POSSIBLY BATTERY CABINET OR |
| | GENERATOR. THE PROPOSED SCOPE OF WORK NEEDS TO BE |
| | SPECIFIC TO THE LOCATION. THERE ARE TOO MANY UNKNOWNS |
| | AT THIS TIME FOR THE WORK. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2, 106.5. ( |
| | ADMINISTRATIVE SECTIONS FOR ADDITIONAL INFORMATION, |
| | CLARITY AND COORDINATION OF PLANS. |
| | NEC 2005 ALL CHAPTERS AS APPLICABLE AS THE SCOPE IS NOT |
| | CLEAR. ALSO SEE NOTES #2 ABOVE. |
| | |
| | 5) NOTE: THE SEAL ON THE ELECTRICAL PLANS ARE NOT CLEAR |
| | AND VISIBLE. EVEN USE OF LEAD RUB DOES NOT IDENTIFY THE |
| | REQUIRED INFORMATION ON SAID SEAL. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002, .001 AND FLORIDA |
| | STATUTES 471.025. ALL INFORMATION ON SEALS NEEDS TO BE |
| | CLEAR AND VISIBLE. |
| | |
| | 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR ANY PROPOSED TRANSFER SWITCH AUTOMATIC, |
| | MANUAL, LEGALLY REQUIRED OR OPTIONAL STAND-BY. |
| | 90.7, 110.3, 701.7, 702.6 |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |