2009-03-04 13:21:34REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2007 CODE FAMILY W/ 2009 REVISIONS
  
  
 1. THE SCOPE OF WORK AS STATED ON THE PLANS IS UNCLEAR.
 IN SOME LOCATIONS THE PLANS REFERENCE THE INSTALLATION
 OF A 30KW GENERATOR WHILE OTHERS REFERENCE A 60 KW
 GENERATOR. WHICH IS CORRECT? PLEASE CLARIFY AND
 COORDINATE PLANS IN ACCORDANCE WITH FBC-B 106.1.1 AND
 FBC-M 304.1.
  
 2. NO SUBMITTAL DATA WAS PROVIDED FOR THE PROPOSED
 GENERATOR OR FUEL STORAGE SYSTEM. PROVIDE SUBMITTAL
 DATA FOR THE PROPOSED GENERATOR AND FUEL STORAGE.
 GENERATOR AND FUEL STORAGE SHALL BE IN COMPLIANCE WITH
 FBC-M SECTION 915.
  
 3. PLEASE UPDATE ALL REFERENCED CODES ON THE PLANS.
 THERE HAS BEEN NO APPLICATION FOR PERMIT SUBMITTED AT
 THIS TIME. ANY APPLICATION FOR PERMIT SUBMITTED AFTER
 MARCH 1, 2009 IS SUBJECT TO THE REQUIREMENTS OF THE
 2007 FLORIDA BUILDING CODE WITH 2009 REVISIONS. IN
 ADDITION, THE 2007 FLORIDA FIRE PREVENTION CODE IS IN
 EFFECT AS OF DECEMBER 31, 2008. PLEASE CORRECT THESE
 AND ALL OTHER REFERENCED CODES AND STANDARDS ON THE
 PLANS.
  
 NOTE: THE SIZE OF THE FUEL TANK FOR THE PROPOSED
 GENERATOR IS NOT KNOWN AT THIS TIME. ANY ABOVE GROUND
 FUEL TANK INSTALLATION >550 GALLONS MUST BE APPROVED BY
 THE PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCE MANAGEMENT (DERM). IF THE PROPSED FUEL TANK
 EXCEEDS 550 GALLONS, PLANS SHALL BE APPROVED BY PBC
 DERM PRIOR TO SUBMISSION TO THE CITY FOR PERMIT. FOR
 MORE INFORMATION PLEASE VISIT
 HTTP://WWW.PBCGOV.COM/ERM/
  