| 2009-03-04 13:21:34 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| | ACTION: DENIED |
| | |
| | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| | FBC 2007 CODE FAMILY W/ 2009 REVISIONS |
| | |
| | |
| | 1. THE SCOPE OF WORK AS STATED ON THE PLANS IS UNCLEAR. |
| | IN SOME LOCATIONS THE PLANS REFERENCE THE INSTALLATION |
| | OF A 30KW GENERATOR WHILE OTHERS REFERENCE A 60 KW |
| | GENERATOR. WHICH IS CORRECT? PLEASE CLARIFY AND |
| | COORDINATE PLANS IN ACCORDANCE WITH FBC-B 106.1.1 AND |
| | FBC-M 304.1. |
| | |
| | 2. NO SUBMITTAL DATA WAS PROVIDED FOR THE PROPOSED |
| | GENERATOR OR FUEL STORAGE SYSTEM. PROVIDE SUBMITTAL |
| | DATA FOR THE PROPOSED GENERATOR AND FUEL STORAGE. |
| | GENERATOR AND FUEL STORAGE SHALL BE IN COMPLIANCE WITH |
| | FBC-M SECTION 915. |
| | |
| | 3. PLEASE UPDATE ALL REFERENCED CODES ON THE PLANS. |
| | THERE HAS BEEN NO APPLICATION FOR PERMIT SUBMITTED AT |
| | THIS TIME. ANY APPLICATION FOR PERMIT SUBMITTED AFTER |
| | MARCH 1, 2009 IS SUBJECT TO THE REQUIREMENTS OF THE |
| | 2007 FLORIDA BUILDING CODE WITH 2009 REVISIONS. IN |
| | ADDITION, THE 2007 FLORIDA FIRE PREVENTION CODE IS IN |
| | EFFECT AS OF DECEMBER 31, 2008. PLEASE CORRECT THESE |
| | AND ALL OTHER REFERENCED CODES AND STANDARDS ON THE |
| | PLANS. |
| | |
| | NOTE: THE SIZE OF THE FUEL TANK FOR THE PROPOSED |
| | GENERATOR IS NOT KNOWN AT THIS TIME. ANY ABOVE GROUND |
| | FUEL TANK INSTALLATION >550 GALLONS MUST BE APPROVED BY |
| | THE PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL |
| | RESOURCE MANAGEMENT (DERM). IF THE PROPSED FUEL TANK |
| | EXCEEDS 550 GALLONS, PLANS SHALL BE APPROVED BY PBC |
| | DERM PRIOR TO SUBMISSION TO THE CITY FOR PERMIT. FOR |
| | MORE INFORMATION PLEASE VISIT |
| | HTTP://WWW.PBCGOV.COM/ERM/ |
| | |