Plan Review Notes
Plan Review Notes For Permit 09020254
Permit Number 09020254
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-03-04 14:37:12***DENIED***
  
 1) WORK TO COMPLY WITH THE FLORIDA FIRE PREVENTION
 CODE, 2007 COMPRISING OF NFPA 101, 2006 AND NFPA 1,
 2006. THIS CURRENT EDITION WAS ADOPTED ON DECEMBER 31,
 2008.
  
 2) ILLUSTRATE THE LOCATION OF THE GENERATOR AND
 ASSOCIATED EQUIPMENT AND EXHAUST TERMINUS AS IT RELATES
 TO MEANS OF EGRESS AND BUILDING OPENINGS.
  
 3) PROVIDE INFORMATION INDICATING WHAT LIFE SAFETY
 EQUIPMENT WILL BE CONNECTED TO THE GENERATOR.
  
 4) IN ADDITION TO OTHER APPLICABLE LISTED CODES, WORK
 TO COMPLY WITH NFPA 30, 2003.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756