| Date |
Text |
| 2009-02-23 09:49:17 | BUILDING PLAN REVIEW |
| | PERMIT: 09020254 |
| | ADD: 6246 45TH STREET |
| | CONT:? |
| | TEL: (813)843-1605 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4) (2004 FBC) 106.1 2004 FBC 1609.1.3 PLEASE PROVIDE |
| | INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST |
| | THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING. THE |
| | ANCHORAGE DESIGN SHALL BE PER ASCE 7-02 1603.1.4. |
| | |
| | 5) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| | SIZE OF GENERATOR(WXL), PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION. |
| | |
| | 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR |
| | VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE |
| | VENTS, ETC. |
| | |
| | 7) THE WIND SPEED INFORMATION INDICATED ON THE PLANS |
| | STATES 130MPH. WEST PALM BEACH IS LOCATED IN THE 140MPH |
| | REGION PER FIGURE1609. CORRECT THE WIND LOAD |
| | INFORMATION TO SHOW THE CORRECT INFORMATION. |
| | |
| | 8) INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED & |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES |
| | AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | NOTE: A PERMIT WILL NOT BE ISSUED UNTIL A CERTIFIED |
| | CONTRACTOR IS SIGNED ON THE APPLICATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |
| | |