| 2009-02-23 17:37:02 | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLETE GROUNDING |
| | ELECTRODE SYSTEM. MUST INCLUDE ALL MINIMUMS PER |
| | 250.50,250.104, 250.53 ETC |
| | FOUNDATION/ FOOTER STEEL, METALLIC COLD WATER SYSTEMS, |
| | BUILDING STEEL ETC |
| | |
| | 2) NOTE: THE ELECTRICAL SITE PLAN DOES NOT INCLUDE ANY |
| | REVISED LOCATIONS FOR SERVICE ENTRANCE CONDUITS. THERE |
| | WERE COMMENTS ON THE BASE BUILDING WHICH WOULD REVISE |
| | POSSIBLE LOCATIONS AND CONDUITS TO BE INSTALLED IN |
| | FOUNDATION AND SLAB. |
| | PLEASE SEE COMMENTS ON BASE BUILDING WITH RESPECT TO |
| | 230.70 FOR DISCONNECTING MEANS LOCATION. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |