| Date |
Text |
| 2009-02-13 17:37:31 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS L-3, L-4 & L-5 THE ADDRESS OF RECORD OF THE |
| | DESIGN PROFESSIONAL ON THE FLORIDA STATE DBPR WEBSITE, |
| | (10748 DEERWOOD PARK BLVD. SOUTH JACKSONVILLE, FL) DOES |
| | NOT REFLECT THE ADDRESS INDICATED ON THE TITLE BLOCKS, |
| | (1715 N. WESTSHORE BLVD. TAMPA FLORIDA). FAC |
| | 61G1-16.004(1) & FS 481.306. PLEASE UPDATE THE TITLE |
| | BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING PLANS |
| | FOR REVIEW. |
| | |
| | 1. SHT L-3 PLEASE INDICATE THE LOCATION OF THE BACKFLOW |
| | PREVENTER AND THE RAIN SENSOR ON THE IRRIGATION PLAN. |
| | SECTIONS 106.1.2 AND APPENDIX F(J) AS WELL AS FS |
| | 3373.62. PLEASE INDICATE IF THERE WILL BE A SEPARATE |
| | METER FOR THE IRRIGATION. IF CONNECTING TO THE WATER |
| | SERVICE FOR THE BUILDING, THEN A REDUCED PRESSURE |
| | BACKFLOW CAN BE USED. TABLE 608.1. (SEE CIVIL SHEET C7 |
| | UTILITY DETAIL |
| | |
| | 3. SHT L-4 DETAIL 5/L-04 DOUBLE CHECK ASSEMBLY IS NOT |
| | APPROVED. AN RPZV BACKFLOW PREVENTOR IS REQUIRED. |
| | SECTION 608.13.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |