| 2009-07-28 13:34:44 | BUILDING PLAN REVIEW |
| | PERMIT: 09020194 |
| | ADD: 309 CLEMATIS ST. |
| | CONT: PLAN REVIEW / VON ESSELBORN |
| | TEL: (561)951-6729 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | 2) MISSING ARCHITECTURAL SHEETS, THERE IS NO |
| | INFORMATION ON THE KITCHEN AS TO FLOOR, WALL NOR |
| | CEILING FINISHES, THICKNESS OF FINSIHES NOR FIRE RAING |
| | OF FINISHES. |
| | 106.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS: |
| | (5) FIRE SUPRESSION SYSTEMS |
| | (9) ROOF/ WALL & FLOOR INSULATION |
| | (11) INTERIOR REQUIREMENTS SHALL INCLUDE FLAME SPREAD |
| | AND SMOKE DEVELOPMENT |
| | LIGHT AND VENTILATION |
| | (12) SPECIAL SYSTEMS: POSIBLE LIFTS |
| | |
| | 3) MASTER PLAN 08060519 SHEET A-8.1 INDICATES FUTURE |
| | ROOF EXHAUST FAN, NO INFORMATION WAS SUBMITTED FOR THE |
| | ROOF CURB, FAN EXHAUST ASSEMBLY, FOR WIND. PLEASE |
| | SSUBMIT STRUCTURAL INFORMATION HOW THE FAN WILL BE |
| | ATTACHED TO THE STRUCTURAL COMPONENTS OF THE BUILDING. |
| | COMPONENTS AND CLADDING. 106.3.5.1.1(8) STRUCTURAL |
| | REQUIREMENTS. |
| | |
| | 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 4A) EXHAUST FANS |
| | 4B) PRE-MANUFACTURED A/C STANDS |
| | |
| | 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |