| 2009-03-26 09:04:08 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THIS PLAN HAS BEEN REVIEWED FOR COMPLIANCE WITH THE |
| | ABOVE LISTED CODES. PLEASE MAKE THE FOLLOWING |
| | CORRECTIONS PRIOR TO RESUMITTING PLANS: |
| | |
| | 1. WHAT IS THE DISTANCE OF THE KITCHEN EXHAUST FAN FROM |
| | ADJACENT BUILDING AND PROPERTY LINE? EXHAUST OUTLETS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET HORIZONTALLY |
| | FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS, |
| | ADJACENT BUILDINGS, ADJACENT PROPERTY LINES AND AIR |
| | INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE WITH |
| | FBC-M 506.3.12.3. |
| | |
| | 2. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED |
| | TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER |
| | COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M |
| | 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL |
| | OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, |
| | BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED |
| | METHODS IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 3. FAN APPEARS TO BE NEXT TO THE ROOF EDGE. GUARDS |
| | SHALL BE PROVIDED WHERE FANS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A ROOF |
| | EDGE IN ACCORDANCE WITH FBC-M 304.10. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF THE |
| | FAN AND THE TOP OF THE GUARD SHALL BE LOCATED NOT LESS |
| | THAN 42 INCHES ABOVE THE ELEVATED SURFACE ADJACENT TO |
| | THE GUARD. THE GUARD SHALL BE CONSTRUCTED IN ACCORDANCE |
| | WITH THE REQUIREMENTS FOR GUARDS SPECIFIED IN THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4. THE PLAN SHOWS THE MANUAL PULL STATION (ACTUATION |
| | DEVICE) NEXT TO THE HOOD. THE MANUAL ACTUATION DEVICE |
| | SHALL BE LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE |
| | COOKING AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 |
| | FEET FROM THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH |
| | FBC-B 904.11.1. THE MANUAL ACTUATION DEVICE SHALL BE |
| | INSTALLED NOT MORE THAN 48 INCHES OR LESS THAN 42 |
| | INCHES ABOVE THE FLOOR AND SHALL CLEARLY IDENTIFY THE |
| | HAZARD PROTECTED. |
| | |
| | 5. EXHAUST FAN AND CURB SHALL BE DESIGNED AND INSTALLED |
| | FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. |
| | PROVIDE MANUFACTURER???S DATA FOR FAN WIND RESISTANCE |
| | AND ATTACHMENT DETAIL FOR CURB-TO-BUILDING AND |
| | FAN-TO-CURB. |
| | |
| | 6. PLAN SHOWS MAKE-UP AIR DUCTS FOR KITCHEN EXHAUST BUT |
| | THE SOURCE OF THE MAKE-UP AIR AND THE MAKE-UP AIR FAN |
| | ARE NOT SHOWN ON PLANS. THE EXHAUST AND MAKEUP AIR |
| | SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED TO INSURE |
| | THAT MAKEUP AIR IS PROVIDED WHENEVER THE EXHAUST SYSTEM |
| | IS IN OPERATION. MAKEUP AIR INTAKE OPENING LOCATIONS |
| | SHALL COMPLY WITH SECTIONS 401.4 AND 401.4.1 IN |
| | ACCORDANCE WITH FBC-M 508.1. |
| | |
| | 7. FLOOR PLAN SHOWS THE KITCHEN EXHAUST DUCT AS 12X12 |
| | WHILE THE ELEVATION PLAN SHOWS THE EXHAUST DUCT AS |
| | 10X12. WHICH IS CORRECT? PLEASE CLARIFY. |
| | |
| | 8. THE ELEVATION PLAN CALLS FOR A 24X14 FIRE RATED |
| | CHASE FOR A 10X12 DUCT. THE ELEVATION PLAN REFERENCES |
| | ARCHITECTURAL PLAN FOR CHASE DETAIL. NO ARCHITECTURAL |
| | PLANS WERE PROVIDED FOR THIS REVIEW. WHILE THIS |
| | ENCLOSURE MAY OR MAY NOT BE REQUIRED BY CODE (SEE |
| | SECTION 506.3.6 FOR CLEARANCE REQUIREMENTS AND 506.3.10 |
| | FOR DUCT ENCLOSURE REQUIREMENTS), THE SIZES SHOWN ON |
| | PLANS WOULD NOT PROVIDE THE REQUIRED MINIMUM CLEARANCES |
| | FOR A DUCT ENCLOSURE. THE ENCLOSURE SHALL BE SEPARATED |
| | FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A MAXIMUM OF |
| | 12 INCHES IN ACCORDANCE WITH FBC-M 506.3.10. THIS |
| | ENCLOSURE SHALL ALSO BE VENTED TO THE OUTSIDE OF THE |
| | BUILDING THROUGH THE USE OF WEATHER-PROTECTED OPENINGS. |
| | |
| | 9. NO INFORMATION WAS PROVIDED REGARDING THE PROPOSED |
| | WALK-IN COOLER. PROVIDE MANUFACTURER???S SUBMITTAL DATA |
| | AND SHOW THE LOCATION OF ALL RELATED EQUIPMENT |
| | (INCLUDING REMOTE CONDENSER), PIPING AND CONDENSATE |
| | DISPOSAL IN ACCORDANCE WITH FBC-M 304.1 AND FBC-B |
| | 106.1.1. |
| | |