2009-02-10 11:03:50RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED
 BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS
 IMPACT PROTECTION. SEE ATTACHED SAMPLE AND COMPLETE ALL
 THE REQUIRED INFORMATION.
 ***NOTE: ON SHEET 2 OF 6 OF NOA 05-0713.03 SUBMITTED
 WALL MOUNT SECTION "A" WAS HIGHLIGHTED AS THE TYPE OF
 INSTALLATION TO BE USED. CONNECTION TYPE (C2)
 HIGHLIGHTED ON SHEET 5 OF 6 DOESN'T CORRESPOND TO THE
 CONNECTION TYPE HIGHLIGHTED ON SHEET 2 OF 6. TAKE THIS
 IN CONSIDERATION WHEN COMPLETING THE INSTALLATION
 SCHEDULE. MAKE SURE CORRECT INFORMATION IS SUBMITTED TO
 AVOID DELAYS, CONFLICTS AND FUTURE RE-SUBMITTAL FEES.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW CONSIDERING THE AMOUNT OF OPENINGS AND TOTAL SQUARE
 FOOTAGE. . UPDATE VALUATION AS REQUIRED BY SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
  
 4- CLEARLY IDENTIFY TYPE OF ROOM WHERE EMERGENCY EGRESS
 DOORS ARE SHOWN TO VERIFY COMPLIANCE WITH SEC. R310.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  