| 2009-04-21 12:46:08 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET MEP-1 UNLESS OTHERWISE | | | NOTED. | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW***INDICATES | | | FURTHER EXPLANATION OF PREVIOUS COMMENT | | | | | | 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED | | | FROM THE FIRST MEANS OF DISCONNECT TO THE PANELS PER | | | 250.118, SIZED PER 250.122***} THE EQUIPMENT GROUND | | | BETWEEN THE METER AND DISCONNECT A ON THE RISER DIAGRAM | | | CREATES A PARALLEL PATH TO GROUND WITH THE NEUTRAL AND | | | MUST BE REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT | | | GROUND ARE TO BE RAN FROM THE FIRST MEANS OF | | | DISCONNECT. 250.6. THERE IS BO EQIPMENT GROUND RAN TO | | | PANEL B.. | | | | | | 4} PER 240.24(E) NOT LOCATED IN BATHROOMS IN DWELLING | | | UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND | | | MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY | | | OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN | | | BATHROOMS.***PANEL "B" MUST BE MOVED TO COMPLY WITH | | | THIS ARTICLE***IT IS NOW IN THE CLOSET IN VIOLATION OF | | | 240.24(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | | | | |
|