2009-04-21 12:46:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1 UNLESS OTHERWISE
 NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW***INDICATES
 FURTHER EXPLANATION OF PREVIOUS COMMENT
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANELS PER
 250.118, SIZED PER 250.122***} THE EQUIPMENT GROUND
 BETWEEN THE METER AND DISCONNECT A ON THE RISER DIAGRAM
 CREATES A PARALLEL PATH TO GROUND WITH THE NEUTRAL AND
 MUST BE REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT
 GROUND ARE TO BE RAN FROM THE FIRST MEANS OF
 DISCONNECT. 250.6. THERE IS BO EQIPMENT GROUND RAN TO
 PANEL B..
  
 4} PER 240.24(E) NOT LOCATED IN BATHROOMS IN DWELLING
 UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND
 MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.***PANEL "B" MUST BE MOVED TO COMPLY WITH
 THIS ARTICLE***IT IS NOW IN THE CLOSET IN VIOLATION OF
 240.24(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  