 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN
 INCLUDING THE DISCONNECTS SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THE GROUNDING ELECTRODE SYSTEM IS INSTALLED AT THE
 METER AND SHOULD GO TO FOOTER STEEL AT THAT POINT. THE
 GROUND RODS AT THE PANELS WOULD VIOLATE 250.24(A)(5)
 LOAD-SIDE GROUNDING CONNECTIONS A GROUNDING CONNECTION
 SHALL NOT BE MADE TO ANY GROUNDED CONDUCTOR ON THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS-.
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANELS PER
 250.118, SIZED PER 250.122.
  
 4} PER 240.24(E) NOT LOCATED IN BATHROOMS IN DWELLING
 UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND
 MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.***PANEL "B" MUST BE MOVED TO COMPLY WITH
 THIS ARTICLE.
  
 5} THERE IS A RECEPTACLE SHOWN IN THE DOORWAY TO THE
 BEDROOM, SHOW CORRECT LOCATION PER 210.52.
  
 6} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.*** LOCATE ON THE PLANS.
  
 7} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14 FOR THE CONDENSING UNIT.
  
 8} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE
 INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED
 TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.*** THE
 LOAD CALCULATION INDICATES 800 VA.
  
 9} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. ALSO
 SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  