| 2009-03-17 15:43:35 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 3- OWES $70.74 FOR UPDATED PERMIT VALUATION AS REQUIRED |
| | BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | C) ROOF SHINGLES. |
| | |
| | D) SHUTTERS IF SINGLE HUNG WINDOWS DON'T HAVE IMPACT |
| | GLAZING. |
| | ALSO, PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE. |
| | SEE ATTACHED COPY. AND, CLEARLY MARK ON SHUTTERS |
| | DRAWINGS SPECIFIC MOUNTING CONDITIONS AND ANCHOR TYPE |
| | AND SPACING TO BE USED. |
| | |
| | 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- SHEET A-2: |
| | A) SPECIFY SAFETY GLAZING FOR WINDOW IN MASTER |
| | BATHROOM. SEC. R308.4 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) WINDOW ON EXISTING BEDROOM IS BLOCKED TO ALLOW FOR |
| | NEW CLOSET. SPECIFY SIZE OF OPENING TO BE BLOCKED AND |
| | SIZE OF EXISTING WINDOW TO REMAIN TO VERIFY COMPLIANCE |
| | WITH THE EGRESS REQUIREMENTS. SEC. R310 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND SEC. 501.2 OF 2004 FLORIDA |
| | EXISTING BUILDING CODE. |
| | |
| | C) REVISE DOOR AND WINDOW NOTE #7. REVISE ITEMS A, B |
| | AND C AS REQUIRED. CHECK SIZE OF SHIMMING. SEE WINDOW |
| | PRODUCT APPROVAL AND SEC. R613.6 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 7- SHEET S-1: |
| | A) REVISE INFORMATION SHOWN ON FOUNDATION NOTES, |
| | FOUNDATION DETAIL, TYPICAL WALL SECTION AND FOUNDATION |
| | PLAN TO MATCH. REVISE STRENGTH OF CONCRETE AND SIZE OF |
| | WIRE MESH TO MATCH. SEE COMMENTS ON PLANS. |
| | |
| | B) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON TYP. |
| | WALL SECTION. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR MIN. TYPE OF NAIL AND SPACING TO |
| | BE USED. |
| | NOTE: ALSO, COORDINATE THIS INFORMATION WITH DIAPHRAGM |
| | SCHEDULE ON SHEET S-2. |
| | |
| | C) CLARIFY INSTALLATION OF 30# FELT SHOWN ON TYP. WALL |
| | SECTION. WHAT'S "30# BASE FELT TIN-TAGGED (@ 24" O.C. |
| | ON BOTH SIDES OF SHEET)". |
| | |
| | D) SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON TYP. |
| | WALL SECTION AS REQUIRED BY SEC. R602.1.2 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | E) SPECIFY SIZE OF ATTIC VENT TO VERIFY COMPLIANCE WITH |
| | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | F) CLARIFY IF TYPICAL WALL SECTION IS FOR THE NEW |
| | ADDITION OR FOR EXISTING WALL SECTION. WALL SECTION FOR |
| | EXISTING WALL IS NOT REQUIRED. ONLY FOR NEW WALL IS |
| | REQUIRED. REVISE TITLE AS REQUIRED. |
| | |
| | 8- SHEET S-2: |
| | A) ENGINEERING CRITERIA: |
| | * CLARIFY IF BUILDING CATEGORY IIIB IS REFERRING TO THE |
| | CONSTRUCTION TYPE. CONSTRUCTION TYPE IIIB REQUIRES TWO |
| | HOUR FIRE RATING. IS THIS ADDITION A 2 HOUR FIRE RATED |
| | CONSTRUCTION?. CLARIFY REVISE AS REQUIRED. |
| | |
| | ** DOOR AND WINDOWS DESIGN PRESSURES DON'T MATCH THOSE |
| | SHOWN ON SHEET A-2. REVISE AS REQUIRED TO MATCH. |
| | |
| | *** REFER TO 2004 FBC WITH 2007 REVISIONS, NOT 2006. |
| | |
| | B) REVISE ROOF ZONE DIAGRAM: REVISE DIMENSION "A".. |
| | IT'S 4'-0" MIN. SEE FIGURE R301.2(8) NOTE A OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | C) DESIGN PARAMETERS NOTE #5 AND INFORMATION SHOWN ON |
| | TYPICAL WALL SECTION DON'T MATCH. REVISE AS REQUIRED. |
| | |
| | D) UPDATE DESIGN PARAMETERS NOTE #6. REVISE CODE YEAR |
| | AND SPECIFIC SECTIONS AND TABLES TO BE USED. |
| | |
| | E) UPDATE INFORMATION FOR CAST-CRETE UPLIFT |
| | CALCULATIONS. REFER TO CORRECT BUILDING CODE EDITION. |
| | |
| | F) ATTIC SIZE SHOWN ON FRAMING PLAN DOESN'T COMPLY WITH |
| | SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | G) COORDINATE DIAPHRAGM SCHEDULE WITH ITEM # 7B ABOVE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |