| 2009-02-08 12:37:59 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 09020147 |
| | ADD: 1615 PALM BEACH LAKES BLVD |
| | CONT: RCC ASSOCIATES, INC |
| | TEL: (954)691-5385 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1CINFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THE COVERSHEET |
| | FAILS TO INCLUDE THE 2005,2006 AND 2007 SUPPLEMENTS. |
| | |
| | 2) THE COVERSHEET INDICATES CIVIL AND LANDSCAPE PLANS |
| | ARE INCLUDED WITHIN THE SET OF PLANS, BUT NO SUCH PLANS |
| | ARE INCLUDED WITHIN THESE SETS OF PLANS. PLANS CAN NOT |
| | BE CHECKED FOR COMPLIANCE (106.3.5.1.1(1) SITE PARKING) |
| | FOR THE FOLLOWING ITEMS: |
| | |
| | 2A) 1-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: |
| | NEW CONSTRUCTION. |
| | THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS, |
| | STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER |
| | CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON |
| | OCTOBER 1, 1997. |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE |
| | OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE |
| | DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS |
| | ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS |
| | OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY, |
| | EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES, |
| | MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND |
| | AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND |
| | PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS, |
| | ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT |
| | DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC |
| | ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE |
| | SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND |
| | THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT |
| | LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION |
| | BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA |
| | STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST, |
| | AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE |
| | ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY |
| | BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS |
| | OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS |
| | CODE. |
| | AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM |
| | REQUIREMENTS: |
| | (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF |
| | THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE |
| | PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED, |
| | AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE |
| | BUILDING ENTRANCE. |
| | (2) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS, |
| | ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND |
| | ACCESSIBLE SPACES THAT ARE ON THE SAME SITE. |
| | (5) PARKING SPACES: |
| | (A) IF PARKING SPACES ARE PROVIDED FOR SELF-PARKING BY |
| | EMPLOYEES OR VISITORS, OR BOTH, THEN ACCESSIBLE SPACES |
| | COMPLYING WITH SECTION 11-4.6 SHALL BE PROVIDED IN EACH |
| | SUCH PARKING AREA. SUCH SPACES SHALL BE DESIGNED AND |
| | MARKED FOR EXCLUSIVE USE OF THOSE INDIVIDUALS WHO HAVE |
| | A SEVERE PHYSICAL DISABILITY AND HAVE PERMANENT OR |
| | TEMPORARY MOBILITY PROBLEMS THAT SUBSTANTIALLY IMPAIR |
| | THEIR ABILITY TO AMBULATE AND WHO HAVE BEEN ISSUED |
| | EITHER A DISABLED PARKING PERMIT UNDER SECTION 316.1958 |
| | OR 320.0848, FLORIDA STATUTES, OR A LICENSE PLATE UNDER |
| | SECTION 320.084, 320.0842, 320.0843, OR 320.0845, |
| | FLORIDA STATUTES. THE NUMBER OF ACCESSIBLE PARKING |
| | SPACES SHALL COMPLY WITH THE TABLE BELOW |
| | C) IF PASSENGER LOADING ZONES ARE PROVIDED, THEN AT |
| | LEAST ONE PASSENGER LOADING ZONE SHALL COMPLY WITH |
| | SECTION 11-4.6.6. |
| | |
| | |
| | 3) THE COVER SHEET INDICATES THERE TO BE CANOPY PLANS |
| | WITHIN THE SET OF PLANS, THE CANOPY |
| | IS ILLUSTRATED ON THE FLOOR PLAN, ELEVATIONS BUT THE |
| | STRUCTURAL SHEET S-1 HAS A NOTE ??? FOUNDATION AND |
| | CANOPY FRAMING BY OTHERS. THE DESCRIPTION OF THE |
| | PROJECT ON THE PERMIT APPLICATION DOES NOT INDICATE IF |
| | THE CANOPY IS TO BE PART OF THIS PERMIT. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. IF THE CANOPY IS TO BE |
| | PART OF THIS PERMIT THEN PLANS WILL BE REQUIRED |
| | 106.3.5.1.1(8) STRUCTURAL REQUIREMENTS. |
| | |
| | SHEET A5 DETAIL# 4 INDICATES THE CANOPY IS TO BE |
| | SUPPLIED AND INSTALLED BY THE MCGEE CORPORATION, |
| | MATTHEW, N. C. 1-800-526-5589. IF THIS STRUCTURE IS TO |
| | BE BUILT UNDER A SEPARATE PERMIT THEN A LETTER FROM |
| | BOTH THE CGC AND CBC THAT THEY HAVE NO PROBLEMS WITH |
| | THE OTHER WHILE WORKING WITHIN THE SAME SITE, LETTER TO |
| | BE NOTARIZED BY THE QUALIFIER ON THEIR LETTERHEAD. |
| | |
| | 4) SOILS REPORTS, NO SOILS REPORTS WERE SUBMITTED |
| | PROVIDING THE MINIMUM SAFE BEARING VALUE OF THE SOILS. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | SOILS REPORTS SHOULD MAKE REFERENCE TO THE TWO |
| | INDEPENDENT STRUCTURES AND TYPE OF FOOTINGS, BUILDING |
| | AND DRIVE THRU STRUCTURE. |
| | |
| | 5A) NOTE, THESE PLANS WERE PREPARED UNDER THE 2004 FBC |
| | BASE CODE, SO THE PRODUCT APPROVALS TO BE SUBMITTED ARE |
| | TO READ CODE VERSION 2004 NOT 2007 AS LISTED BELOW??? |
| | (1) FL2887-R2/2007 VISTA WALL- PANEL WALL- STOREFRONT |
| | (3 SETS) |
| | (2) FL1601-R5/2007 CARLISLE SYNTEC INCORPORATED (3 |
| | SETS) |
| | |
| | 5B) NOTE, SINCE 3 SETS OF PLANS AND SOME PRODUCT |
| | APPROVALS THESE ARE THE APPROVALS WHERE LESS WERE |
| | SUBMITTED: |
| | (1) GLAZED EXTERIOR DOORS, VISTAWALL INDICATES DOORS |
| | ARE COVERED UNDER A SEPARATE |
| | SUBMISSION |
| | (2) ROOF HATCHES- 1609.6.2.2 COMPONENTS AND CLADDING AS |
| | WELL AS FLORIDA LAW |
| | RULE 9B-72.32(31) (A) PRE-ENGINEERED ROOF ACCESS |
| | HATCHES |
| | (3) WINDOW TYPE ???D??? PROVIDED BY BANK EQUIPMENT |
| | SUPPLIER. |
| | |
| | 5C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5D) WHILE NOT A TRUE PRODUCT APPROVAL IT TIES IN TO |
| | COMPONENTS AND CLADDING, THE RTU UNITS THAT TIE DOWN TO |
| | THE ROOF, PLEASE PROVIDE TWO ITEMS: |
| | (1) THE ACTUAL RESTRAINT FOR THE CURB TO ROOF AND THE |
| | UNIT TO THE CURB, COMPONENTS AND |
| | CLADDING 1609.6.2.2. SHOW COMPLIANCE WITH THE TTIE DOWN |
| | OF THE CURB TO ROOF SYSTEM AND UNIT TO CURB. |
| | (2) DEALS WITH THE ROOF TOP EQUIPMENT: 301.13 FBC |
| | MECHANICAL CODE |
| | WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED |
| | (THE UNITS THEMSELVES) AND INSTALLED TO RESIST WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 6) ROOFING: |
| | 6A) ROOFING PRODUCT APPROVAL CARLISLE SYNTEC |
| | INCORPORATED CORRECT VERSION IS FL1601-R4 |
| | (2004 FBC) THE INFORMATION SUBMITTED IS A GUIDE-SPEC |
| | FOR SURE WELD FULLY ADHERED ROOFING SYSTEM. THERE IS NO |
| | INSTALLATION INFORMATION PROVIDED NOR THE PSF THIS |
| | SYSTEM WILL BE ABLE TO WITHSTAND NOR LIMITATIONS FOR |
| | FASTENER LENGTHS. 1609.6.2.2. |
| | |
| | |
| | 6B) ROOF INSULATION SHEET A5 & A6 BOTH INDICATE THE USE |
| | OF A FIBER FACED POLYISOCYANURATE |
| | ROOF INSULATION WITH A R-VALUE OF 21. PLEASE NOTE THAT |
| | THE MINIMUM R-21 VALUE WILL NEED TO BE AT THE ROOF |
| | DRAINS AND SLOPE UP FROM THERE. PLEASE PROVIDE SHOP |
| | DRAWINGS INDICATING THE DEPTH OF THE INSULATION AT THE |
| | OPPOSITE WALL OF THE ROOF DRAINS. FL 61G1-23.015 (2) |
| | THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC... |
| | |
| | PROVIDE ALSO THE CALCULATIONS FOR FASTENERS. LENGTH OF |
| | FASTENERS IS A CONCERN USING A JOHNS MANSVILLE FESCO |
| | FOAM ALSO A POLYISOCYNURATE AND LAMINATOR BOARD THE |
| | DEPTH OF THE FOAM APPEARS TO BE APPROXIMATELY 3.7 |
| | INCHES AT THE ROOF DRAIN FOR A R-21 AND 14 INCHES AT |
| | THE OPPOSITE WALL 42 FEET AWAY. PLEASE SEE ENCLOSED FL |
| | INFORMAL CODE INTERPRETATIONS. |
| | |
| | 6C) THE A5 & A-6 SHEET INDICATE A R-VALUE OF 21 USING A |
| | POLYISOCYNURATE FOAM WHILE THE ENERGY CALCULATION |
| | INDICATES THE USE OF A AGRIBOARD ROOF INSULATION AGAIN |
| | PLEASE CORRELATE YOUR DATA AND SUBMIT OR RESUBMIT. NOTE |
| | THE AGRIBOARD PANEL INSULATING VALUE OF 25.44 IS A |
| | PANEL 7-7/8??? THAT WOULD STILL NEED ????? PER FOOT OF |
| | (2%)SLOPE FOR THE ROOFING SYSTEMS DRAINAGE |
| | REQUIREMENTS. SECTION 1507.13.1. |
| | |
| | 7) DISCREPANCIES BETWEEN THE ENERGY INPUT DATA REPORT |
| | AND THE ARCHITECTURAL PLANS. THE INPUT DATA REPORT |
| | UNDER WALLS INDICATES 25.6 R-VALUE FOR A |
| | STUCCO/AGRIBOARD/ GYPSUM BOARD WALL SYSTEM WHERE AS |
| | SHEET A5 & A6 BOTH INDICATE THE USE OF STUCCO, CMU, |
| | 1 /12 INCH THICK POLYSTYRENE (R-11) AND 5/8??? GYP |
| | BOARD. PLEASE CORRECT, AND CORRELATE DOCUMENTS. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. 13-400.0.A. |
| | |
| | 8) INPUT DATA REPORT EXTERIOR DOORS IS LEFT BLANK |
| | PLEASE REVIEW SHEET A1 DOOR 120B IS A INSULATED |
| | EXTERIOR METAL DOOR. |
| | |
| | 9) THE INPUT DATA REPORT HAS TAKEN A VALUE OF 4546 SQ |
| | FT FOR CARPET AND RUBBER PAD PLEASE REVIEW SHEET F-1 |
| | INDICATING THE USE OF VCT TILE. PLEASE CORRELATE THE |
| | INPUT DATA REPORT TO PLANS. 13-400.A/ 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 10) SHEET A2 DETAIL 2 INDICATES A SOFFIT TO BE FASTENED |
| | TO DECK ABOVE BUT THERE IS NO INFORMATION AS TO SECURE |
| | THE SOFFIT TO THE DECK ABOVE. |
| | |
| | 11A) SHEET A-5 DETAIL 2 & 9 BOTH INDICATE THE USE OF |
| | SUN SCREEN DETAIL, SHOP DRAWINGS TO BE SIGNED AND |
| | SEALED, PLEASE HAVE THEM DESIGNED TO 140 MPH WIND ZONE, |
| | EXPOSURE ???C???. |
| | 1609.6.2.2 COMPONENTS AND CLADDING. |
| | |
| | 11B) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE |
| | FOR SUPERVISING AND REVIEWING ALL PROJECT DATA, |
| | REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 12) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| | INDICATE ANY COMPLIANCE FOR TERMITE PROTECTION. 1816.1 |
| | TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: ???THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.??? |
| | |
| | |
| | 13A) SHEET A14 DUMPSTER ENCLOSURE IS NOT INDICATED ON |
| | THE STRUCTURAL PLANS, |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE PLAN: |
| | DESIGN PROCEDURE 1609.6.2 |
| | 1.THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3 . THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | 2. AN IMPORTANCE FACTOR, I W , SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.5 . |
| | 3. AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.4 . |
| | 4. A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, L , |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1 (4). |
| | |
| | 13B) SHEET A14 DUMPSTER ENCLOSURE FOOTER DOES NOT |
| | PROVIDE THE STRENGTH OF CONCRETE TO BE PLACED WITHIN |
| | THE FOOTER. 1805.4.2.1 CONCRETE STRENGTH. CONCRETE IN |
| | FOOTINGS SHALL HAVE A SPECIFIED COMPRESSIVE STRENGTH |
| | (F' C) OF NOT LESS THAN 2,500 POUNDS PER SQUARE INCH |
| | (PSI) (17 237 KPA) AT 28 DAYS. |
| | |
| | 14) SHEET S-4 DETAIL# 2 INDICATES LIGHT GAUGE FRAMING |
| | BUT NO MENTION OF SHEATHING. INDICATES SEE |
| | ARCHITECTURAL PLANS. A5 DETAIL# 9 ALSO INDICATES THE |
| | USE OF 5/8 INCH SHEATHING BUT DOES NOT INDICATE WHAT |
| | TYPE OF SHEATHING IS TO BE USED. |
| | |
| | 15) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 16) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL |
| | BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 18) FEE BALANCE OF $8,025.60. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953. |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL |
| | ADDRESSES ARE PUBLIC RECORDS. WRITTEN COMMUNICATIONS TO |
| | OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE |
| | PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. |
| | YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO |
| | PUBLIC DISCLOSURE. |
| | |
| | |
| | |