Plan Review Notes
Plan Review Notes For Permit 09020137
Permit Number 09020137
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-17 16:07:06DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR
 IS REQUIRED ON THE HOT WATER SUPPLY TO THE DISHWASHER.
 SECTION 604.9.
  
 2. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER REQUIRES
 THERMAL EXPANSION CONTROL. SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 3. SHT 1 WATER RISER DIAGRAM. THE P&T VALVE FROM THE
 WATER HEATER. PLEASE INDICATE WHERE THE VALVE
 DISCHARGES. SECTION 504.6.1.
  
 4. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER SHALL BE
 INSTALLED IN A GALVANIZED STEEL OR OTHER METAL PAN OF
 EQUAL CORROSION RESISTANCE OR IN A HIGH-IMPACT PLASTIC
 PAN. SECTION 504.7. ALSO SEE SECTIONS 504.7.1 PAN SIZE
 AND DRAIN AS WELL AS SECTION 504.7.2 PAN DRAIN
 TERMINATION.
  
 5. SHT 1 WASTE RISER DIAGRAM. THE DISHWASHER SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2. -- EACH FIXTURE SHALL BE SEPARATELY
 TRAPPED BY A WATER SEAL TRAP, EXCEPT AS OTHERWISE
 PERMITTED BY THIS CODE. SECTION 1002.1. NO TRAP SHOWN
 AT THE DISHWASHER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  