| 2009-02-17 16:07:06 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | |
| | 1. SHT 1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR |
| | IS REQUIRED ON THE HOT WATER SUPPLY TO THE DISHWASHER. |
| | SECTION 604.9. |
| | |
| | 2. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER REQUIRES |
| | THERMAL EXPANSION CONTROL. SECTION 607.3.2. PLEASE |
| | INDICATE METHOD. |
| | |
| | 3. SHT 1 WATER RISER DIAGRAM. THE P&T VALVE FROM THE |
| | WATER HEATER. PLEASE INDICATE WHERE THE VALVE |
| | DISCHARGES. SECTION 504.6.1. |
| | |
| | 4. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER SHALL BE |
| | INSTALLED IN A GALVANIZED STEEL OR OTHER METAL PAN OF |
| | EQUAL CORROSION RESISTANCE OR IN A HIGH-IMPACT PLASTIC |
| | PAN. SECTION 504.7. ALSO SEE SECTIONS 504.7.1 PAN SIZE |
| | AND DRAIN AS WELL AS SECTION 504.7.2 PAN DRAIN |
| | TERMINATION. |
| | |
| | 5. SHT 1 WASTE RISER DIAGRAM. THE DISHWASHER SHALL |
| | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK |
| | INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH |
| | SECTION 802.2. -- EACH FIXTURE SHALL BE SEPARATELY |
| | TRAPPED BY A WATER SEAL TRAP, EXCEPT AS OTHERWISE |
| | PERMITTED BY THIS CODE. SECTION 1002.1. NO TRAP SHOWN |
| | AT THE DISHWASHER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |