2009-02-15 12:27:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS PROJECT CONSISTD OF A LEVEL 2 ALTERATION IN
 ACCORDANCE WITH FBC-EB 304.1. LEVEL 2 ALTERATIONS SHALL
 DEMONSTRATE COMPLIANCE WITH THE MECHANICAL VENTILATION
 REQUIREMENTS OF THE FBC-M IN ACCORDANCE WITH FBC-EB
 SECTION 609.1. PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL
 RECOFIGURED SPACES WITH OCCUPANT LOADS, OCCUPANCY
 CLASSIFICATIONS AND OUTSIDE AIR QUANTITIES IN
 ACCORDANCE WITH FBC-M SECTION 403.
  