Plan Review Notes
Plan Review Notes For Permit 09020137
Permit Number 09020137
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-10 11:09:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING***SOME
 SPACES INDICATE SWITCHES AS EXISTING WITH NO COMPLIANCE
 FOR SPACE CONTROL 30 MINUTE RESTRICTIONS.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 LIGHTING CIRCUITS, SHEET #2.
  
 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN
 ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN
 AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL
 TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH
 ARTICLE 590 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  