| Plan Review Notes For Permit 09020137 |
| Permit Number |
09020137 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-10 11:09:38 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 13-415.1.ABC.1.2 SPACE CONTROL. | | | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL | | | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY | | | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH | | | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED | | | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING***SOME | | | SPACES INDICATE SWITCHES AS EXISTING WITH NO COMPLIANCE | | | FOR SPACE CONTROL 30 MINUTE RESTRICTIONS. | | | | | | 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR | | | LIGHTING CIRCUITS, SHEET #2. | | | | | | 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN | | | ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN | | | AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL | | | TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH | | | ARTICLE 590 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|