| 2009-07-16 10:54:44 | REVISED M1.0, M2.1, M6.1 DELTA 4 **PROVISO** | | | | | | PAGE M6.1: IN ORDER TO USE THE SUB-DUCT SYSTEM IN LIEU | | | OF FIRE/SMOKE DAMPERS AT SHAFT PENETRATIONS FOR EF-18, | | | THE FAN MUST BE SUPPLIED WITH BUILDING EMERGENCY POWER | | | IN ACCORDANCE WITH FBC-M 607.5.5.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|