Plan Review Notes
Plan Review Notes For Permit 09020136
Permit Number 09020136
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-24 20:14:54** PROVISO **
  
 1) NOTE: SOME CODE EDITIONS WERE CORRECTED HOWEVER THE
 SHEET M0.1 STILL INDICATES THE 2002 NFPA-70
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1 AND .1.2.
 ROOMS/AREAS 242, 243 AND 247 STILL INDICATE STANDARD
 SINGLE POLE SWITCHES. PLEASE ADDRESS MINIMUM CODE AND
 RESPOND ACCORDINGLY.
  
 3) NOTE: PLEASE SEE FURNITURE/DESK/COUNTER SHOWN ON
 E4.1 AND ON POWER PLANS WHICH IS SHOWN DIRECTLY IN
 FRONT OF THE ELECTRICAL PANELS 4CR1 AND 4CR2. THIS DOES
 NOT MINIMUM CODE COMPLIANCE FOR WORKING CLEARANCES.
 PLEASE SEE 110.26. PLEASE RELOCATE EITHER THE PANELS OR
 THE FURNITURE/DESK/COUNTER.
  
 ** PLANS NEED TO BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION. ANY INSTALLATION NOT DONE PER PROVISO
 ISSUED ON PLANS MAY RESULT IN A DELAY OF PROJECT.
 PLEASE CALL IF THERE ANY QUESTIONS.
  