| Plan Review Notes For Permit 09020136 |
| Permit Number |
09020136 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-03-24 20:14:54 | ** PROVISO ** | | | | | | 1) NOTE: SOME CODE EDITIONS WERE CORRECTED HOWEVER THE | | | SHEET M0.1 STILL INDICATES THE 2002 NFPA-70 | | | | | | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1 AND .1.2. | | | ROOMS/AREAS 242, 243 AND 247 STILL INDICATE STANDARD | | | SINGLE POLE SWITCHES. PLEASE ADDRESS MINIMUM CODE AND | | | RESPOND ACCORDINGLY. | | | | | | 3) NOTE: PLEASE SEE FURNITURE/DESK/COUNTER SHOWN ON | | | E4.1 AND ON POWER PLANS WHICH IS SHOWN DIRECTLY IN | | | FRONT OF THE ELECTRICAL PANELS 4CR1 AND 4CR2. THIS DOES | | | NOT MINIMUM CODE COMPLIANCE FOR WORKING CLEARANCES. | | | PLEASE SEE 110.26. PLEASE RELOCATE EITHER THE PANELS OR | | | THE FURNITURE/DESK/COUNTER. | | | | | | ** PLANS NEED TO BE REVISED BEFORE ROUGH ELECTRICAL | | | INSPECTION. ANY INSTALLATION NOT DONE PER PROVISO | | | ISSUED ON PLANS MAY RESULT IN A DELAY OF PROJECT. | | | PLEASE CALL IF THERE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|