Plan Review Notes
Plan Review Notes For Permit 09020136
Permit Number 09020136
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-03-12 11:37:09***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 EFFECTIVE ON DECEMBER 31, 2008. SHT LS-1
  
 2) LIFE SAFETY SHEETS INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING TO BE CLASS B BUT
 SHOW A FLAME SPREAD INDEX OF 0-25 WHICH WOULD SUGGEST
 CLASS A.
  
 3) PLEASE NOTE THAT THE USE OF THE LIFE SAFETY ANNEX
 SECTION DOES NOT SUPPORT PRESCRIPTIVE CODE
 REQUIREMENTS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) WORK SHALL NOT INTERFERE WITH THE BUILDING FIRE
 PROTECTION SYSTEMS. ALL REQUIRED MEANS OF EGRESS TO BE
 MAINTAINED.
  
 6) WHERE PROVIDED, DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODAL.
  
 8) FIRE SPRINKLER SYSTEM REMODEL TO COMPLY WITH NFPA
 13, 2002.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756