| Plan Review Notes For Permit 09020136 |
| Permit Number |
09020136 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-12 11:37:09 | ***DENIED*** | | | | | | 1) LIFE SAFETY TO COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND | | | NFPA 1, 2006 EFFECTIVE ON DECEMBER 31, 2008. SHT LS-1 | | | | | | 2) LIFE SAFETY SHEETS INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING TO BE CLASS B BUT | | | SHOW A FLAME SPREAD INDEX OF 0-25 WHICH WOULD SUGGEST | | | CLASS A. | | | | | | 3) PLEASE NOTE THAT THE USE OF THE LIFE SAFETY ANNEX | | | SECTION DOES NOT SUPPORT PRESCRIPTIVE CODE | | | REQUIREMENTS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) WORK SHALL NOT INTERFERE WITH THE BUILDING FIRE | | | PROTECTION SYSTEMS. ALL REQUIRED MEANS OF EGRESS TO BE | | | MAINTAINED. | | | | | | 6) WHERE PROVIDED, DUCT SMOKE DETECTORS SHALL INITIATE | | | A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODAL. | | | | | | 8) FIRE SPRINKLER SYSTEM REMODEL TO COMPLY WITH NFPA | | | 13, 2002. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|