| 2009-03-06 12:02:00 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS SHALL STATE THE FOLLOWING CODES. |
| | NFPA-101 2006. ADOPTED BY FAC 69A-60.004 DECEMBER 31ST, |
| | 2008 |
| | NFPA-1 2006 FAC 69A-60.003 SAME. |
| | |
| | SOME SHEETS SUCH AS MECHANICAL STILL STATE THE 2002 |
| | NEC, SOME OTHERS STATE 2003 NFPA-101. |
| | |
| | ** PLEASE ADJUST AND REVISE. |
| | BASED ON THE TIME OF PERMIT APPLICATION THE BUILDING |
| | CODE SHOW SHOULD BE 2004 W/ 2007 REVISIONS. |
| | |
| | 2) NOTE: PLEASE INCLUDE COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | |
| | 3) NOTE: PLEASE INCLUDE REQUIRED LIGHTING CONTROLS FOR |
| | NEW AREAS PER FBC 13-415.1.ABC.1.1, .1.2. SOME AREAS |
| | SUCH AS ROOMS 250, 249 ETC WHICH ARE NOT 24HR USE AND |
| | NOT PATIENT CARE SHOW STANDARD SINGLE POLE DEVICES. |
| | PLEASE ADJUST AND REVISE. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |