Plan Review Notes
Plan Review Notes For Permit 09020136
Permit Number 09020136
Review Stop B
Sequence Number 1
Notes
Date Text
2009-02-27 10:59:06BUILDING PLAN REVIEW
 PERMIT: 09020136
 ADD: 315 S FLAGLER DR
 CONT: J. JAY ROTHE, INC.
 TEL: (561) 389-4137
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) LS-1 INDICATES APPLICABLE CODES, UNDER THIS HEADING
 THE WORDING OF FAMILY OF 2004 FLORIDA BUILDING CODE,
 WHICH WOULD INCLUDE THE EXISTING BUILDING CODE,
 UNDERTHE EXISTING BUILDING CODE THE DESIGNER OF RECORD
 IS TO INDICATE AS TO WHAT LEVEL OF ALTERATION THE
 PROJECT WILL CONFORM TO? EXISTING BUILDING CODE 301.5.
 WITH THIS INFORMATION LACKING A THROUGH REVIEW MAY NOT
 BE POSSIBLE. FOR THIS REVIEW IT WILL BE ASSUMED THE
 LEVEL OF ALTERATION SHALL BE CONSIDERED A LEVEL TWO
 ALTERATION WITH THE RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY ADDED EQUIPMENT.
 304.1. EXISTING BUILDING CODE.
  
 3) PLEASE REVIEW SHEET A-1.01 AND SECTION 603.3 OF THE
 EXISTING BUILDING CODE . SMOKE BARRIERS. SMOKE BARRIERS
 IN GROUP I-2 OCCUPANCIES SHALL BE INSTALLED WHERE
 REQUIRED BY SECTIONS 603.3.1 & 603.3.2.
 603.3.1 COMPARTMENTATION. SEE SECTION 407 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 603.3.2 FIRE-RESISTANCE RATING. THE SMOKE BARRIERS
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, OR THE FLORIDA FIRE PREVENTION CODE.
  
  
 3A) UNDER THE HEADING SECTIOIN 407.2.1 SPACES OF
 UNLIMITED AREA SPLEASE REVIEW 407.2.1(1-4). (1) THE
 SPACES ( WAITING ROOMS AND SIMILAR SPACES) ARE NOT
 OCCUPIED FOR PATIENT SLEEPING UNITS, TREATMENT ROOMS,
 HAZARDOUS OR INCIDENTIAL USE AREAS AS DEFINED IN
 SECTION 302.1.1. THIS AREA CLEALY IS IN DIRECT CONTACT
 WITH SLEEPING UNITS, MECANICAL ROOMS, JANITORS CLOSETS
 AND LINEN ROOMS. PLEASE REVIEW SECTIONS FROM THE CODE
 COMMENTARY AND FIGURE 407.2.1.
  
 3B) THE SECOND CRITERIA IS AUTOMATIC FIRE DETECTION
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTIOIN 907. THIS
 BUILDING IS A HIGHRISE AND WILL NEED TO MEET THE
 REQUIREMENTS OF 907.2.12..2.
 907.2.12.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
 THE OPERATION OF ANY AUTOMATIC FIRE DETECTOR, SPRINKLER
 WATER-FLOW DEVICE OR MANUAL FIRE ALARM BOX SHALL
 AUTOMATICALLY SOUND AN ALERT TONE FOLLOWED BY VOICE
 INSTRUCTIONS GIVING APPROVED INFORMATION AND DIRECTIONS
 ON A GENERAL OR SELECTIVE BASIS TO THE FOLLOWING
 TERMINAL AREAS ON A MINIMUM OF THE ALARMING FLOOR, THE
 FLOOR ABOVE AND THE FLOOR BELOW IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
 1. ELEVATOR LOBBIES.
 2. CORRIDORS.
 3. ROOMS AND TENANT SPACES EXCEEDING 1,000 SQUARE FEET
 (93 M2) IN AREA.
 4. DWELLING UNITS OR SLEEPING UNITS IN GROUP R-2
 OCCUPANCIES.
 5. SLEEPING UNITS IN GROUP R-1 OCCUPANCIES.
 6. AREAS OF REFUGE AS DEFINED IN SECTION 1002.
 EXCEPTION: IN GROUP I-1 AND I-2 OCCUPANCIES, THE ALARM
 SHALL SOUND IN A CONSTANTLY ATTENDED AREA AND A GENERAL
 OCCUPANT NOTIFICATION SHALL BE BROADCAST OVER THE
 OVERHEAD PAGE.
  
 EXISTING BUILDING CODE 604.2.1 HIGH RISE SEE SECTION
 403 FBC, BUILDING. 403.15 SMOKE CONTROL EXCEPTION FOR
 I-2 SHALL COMPLY WITH 407, 419.3.12 AND 420.3.16.
  
 3C) THE THIRD CRITERIA IS THE OPEN CORRIDOR ONTO WHICH
 THE OPEN SPACE ADJOINS THIS SPACE IS TO BE OUTFITTED
 WITH QUICK RESPONCE SPRINKLER HEADS, SHEET FS.02 DOES
 INDICATE THE USE OF QUICK RESPONCE HEADS BUT FS.01 DOES
 INDICATE THE USE OF A R13 SYSTEM THIS AREA IS WITHIN A
 HIGH-RISE BUILDING REQUIRING A FULL NFPA 13 SYSTEM
 PLEASE CORRECT.
  
 3D) AS TO THE FOURTH REQUIREMENT WAITING AREAS AND
 SIMILAR SPACES OPEN TO THE CORRIDORS MUST BE ARRANGED
 SO AS TO NOT OBSTRUCT ACCESS TO THE EXITS, THIS
 CRITERIA HAS BEEN MET.
  
 4) . EXISTING BUILDING CODE 606.1. A BUILDING FACILITY,
 OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH CHAPTER 11
 OF THE FLORIDA BUILDING CODE, BUILDING, ACCESSIBILITY.
 SHEET A-1.01 DETAIL 2 A HI-LOW DRINKING FOUNTAIN, THE
 LOW SECTION OF THE FOUNTAIN INDICATES A MINIMUM CLEAR
 SPACE OF 2'-3" OR 27". THIS WILL BECOME A ABSOLUTE
 HEIGHT IN MOST CASES SINCE WE ALSO HAVE TO REVIEW FOR
 11-4.4.1 PROTRUDING OBJECT WHICH REQUIRES A HEIGTH OF
 NOT MORE THAN 27" FROM THE FINISH FLOOR FOR OBJECTS
 THAT PROTRUDE MORE THAN 4". THE SECOND ISSUE IS WITH
 THE HIGH SIDE OF THE DRINKING FOUNTAIN, HOW WILL THIS
 AREA OF THE DRINKING FOUNTAIN COMPLY WITH THIS SAME
 CODE SECTION. WE HAVE SEEN IN SOME INSTANCES EXTENSION
 OR APRONS DROPPING FROM THE DRINKING FOUNTAIN THAT
 BRINGS THE DRINKING FOUNTAIN INTO COMPLIANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 PASSED PER MEETING WITH ROBERT BROWN 3-19-09