| 2009-02-27 10:59:06 | BUILDING PLAN REVIEW |
| | PERMIT: 09020136 |
| | ADD: 315 S FLAGLER DR |
| | CONT: J. JAY ROTHE, INC. |
| | TEL: (561) 389-4137 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 2) LS-1 INDICATES APPLICABLE CODES, UNDER THIS HEADING |
| | THE WORDING OF FAMILY OF 2004 FLORIDA BUILDING CODE, |
| | WHICH WOULD INCLUDE THE EXISTING BUILDING CODE, |
| | UNDERTHE EXISTING BUILDING CODE THE DESIGNER OF RECORD |
| | IS TO INDICATE AS TO WHAT LEVEL OF ALTERATION THE |
| | PROJECT WILL CONFORM TO? EXISTING BUILDING CODE 301.5. |
| | WITH THIS INFORMATION LACKING A THROUGH REVIEW MAY NOT |
| | BE POSSIBLE. FOR THIS REVIEW IT WILL BE ASSUMED THE |
| | LEVEL OF ALTERATION SHALL BE CONSIDERED A LEVEL TWO |
| | ALTERATION WITH THE RECONFIGURATION OR EXTENSION OF ANY |
| | SYSTEM, OR THE INSTALLATION OF ANY ADDED EQUIPMENT. |
| | 304.1. EXISTING BUILDING CODE. |
| | |
| | 3) PLEASE REVIEW SHEET A-1.01 AND SECTION 603.3 OF THE |
| | EXISTING BUILDING CODE . SMOKE BARRIERS. SMOKE BARRIERS |
| | IN GROUP I-2 OCCUPANCIES SHALL BE INSTALLED WHERE |
| | REQUIRED BY SECTIONS 603.3.1 & 603.3.2. |
| | 603.3.1 COMPARTMENTATION. SEE SECTION 407 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 603.3.2 FIRE-RESISTANCE RATING. THE SMOKE BARRIERS |
| | SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, OR THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | |
| | 3A) UNDER THE HEADING SECTIOIN 407.2.1 SPACES OF |
| | UNLIMITED AREA SPLEASE REVIEW 407.2.1(1-4). (1) THE |
| | SPACES ( WAITING ROOMS AND SIMILAR SPACES) ARE NOT |
| | OCCUPIED FOR PATIENT SLEEPING UNITS, TREATMENT ROOMS, |
| | HAZARDOUS OR INCIDENTIAL USE AREAS AS DEFINED IN |
| | SECTION 302.1.1. THIS AREA CLEALY IS IN DIRECT CONTACT |
| | WITH SLEEPING UNITS, MECANICAL ROOMS, JANITORS CLOSETS |
| | AND LINEN ROOMS. PLEASE REVIEW SECTIONS FROM THE CODE |
| | COMMENTARY AND FIGURE 407.2.1. |
| | |
| | 3B) THE SECOND CRITERIA IS AUTOMATIC FIRE DETECTION |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTIOIN 907. THIS |
| | BUILDING IS A HIGHRISE AND WILL NEED TO MEET THE |
| | REQUIREMENTS OF 907.2.12..2. |
| | 907.2.12.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM. |
| | THE OPERATION OF ANY AUTOMATIC FIRE DETECTOR, SPRINKLER |
| | WATER-FLOW DEVICE OR MANUAL FIRE ALARM BOX SHALL |
| | AUTOMATICALLY SOUND AN ALERT TONE FOLLOWED BY VOICE |
| | INSTRUCTIONS GIVING APPROVED INFORMATION AND DIRECTIONS |
| | ON A GENERAL OR SELECTIVE BASIS TO THE FOLLOWING |
| | TERMINAL AREAS ON A MINIMUM OF THE ALARMING FLOOR, THE |
| | FLOOR ABOVE AND THE FLOOR BELOW IN ACCORDANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | 1. ELEVATOR LOBBIES. |
| | 2. CORRIDORS. |
| | 3. ROOMS AND TENANT SPACES EXCEEDING 1,000 SQUARE FEET |
| | (93 M2) IN AREA. |
| | 4. DWELLING UNITS OR SLEEPING UNITS IN GROUP R-2 |
| | OCCUPANCIES. |
| | 5. SLEEPING UNITS IN GROUP R-1 OCCUPANCIES. |
| | 6. AREAS OF REFUGE AS DEFINED IN SECTION 1002. |
| | EXCEPTION: IN GROUP I-1 AND I-2 OCCUPANCIES, THE ALARM |
| | SHALL SOUND IN A CONSTANTLY ATTENDED AREA AND A GENERAL |
| | OCCUPANT NOTIFICATION SHALL BE BROADCAST OVER THE |
| | OVERHEAD PAGE. |
| | |
| | EXISTING BUILDING CODE 604.2.1 HIGH RISE SEE SECTION |
| | 403 FBC, BUILDING. 403.15 SMOKE CONTROL EXCEPTION FOR |
| | I-2 SHALL COMPLY WITH 407, 419.3.12 AND 420.3.16. |
| | |
| | 3C) THE THIRD CRITERIA IS THE OPEN CORRIDOR ONTO WHICH |
| | THE OPEN SPACE ADJOINS THIS SPACE IS TO BE OUTFITTED |
| | WITH QUICK RESPONCE SPRINKLER HEADS, SHEET FS.02 DOES |
| | INDICATE THE USE OF QUICK RESPONCE HEADS BUT FS.01 DOES |
| | INDICATE THE USE OF A R13 SYSTEM THIS AREA IS WITHIN A |
| | HIGH-RISE BUILDING REQUIRING A FULL NFPA 13 SYSTEM |
| | PLEASE CORRECT. |
| | |
| | 3D) AS TO THE FOURTH REQUIREMENT WAITING AREAS AND |
| | SIMILAR SPACES OPEN TO THE CORRIDORS MUST BE ARRANGED |
| | SO AS TO NOT OBSTRUCT ACCESS TO THE EXITS, THIS |
| | CRITERIA HAS BEEN MET. |
| | |
| | 4) . EXISTING BUILDING CODE 606.1. A BUILDING FACILITY, |
| | OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH CHAPTER 11 |
| | OF THE FLORIDA BUILDING CODE, BUILDING, ACCESSIBILITY. |
| | SHEET A-1.01 DETAIL 2 A HI-LOW DRINKING FOUNTAIN, THE |
| | LOW SECTION OF THE FOUNTAIN INDICATES A MINIMUM CLEAR |
| | SPACE OF 2'-3" OR 27". THIS WILL BECOME A ABSOLUTE |
| | HEIGHT IN MOST CASES SINCE WE ALSO HAVE TO REVIEW FOR |
| | 11-4.4.1 PROTRUDING OBJECT WHICH REQUIRES A HEIGTH OF |
| | NOT MORE THAN 27" FROM THE FINISH FLOOR FOR OBJECTS |
| | THAT PROTRUDE MORE THAN 4". THE SECOND ISSUE IS WITH |
| | THE HIGH SIDE OF THE DRINKING FOUNTAIN, HOW WILL THIS |
| | AREA OF THE DRINKING FOUNTAIN COMPLY WITH THIS SAME |
| | CODE SECTION. WE HAVE SEEN IN SOME INSTANCES EXTENSION |
| | OR APRONS DROPPING FROM THE DRINKING FOUNTAIN THAT |
| | BRINGS THE DRINKING FOUNTAIN INTO COMPLIANCE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | PASSED PER MEETING WITH ROBERT BROWN 3-19-09 |