Plan Review Notes
Plan Review Notes For Permit 09020130
Permit Number 09020130
Review Stop B
Sequence Number 1
Notes
Date Text
2009-02-09 13:40:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
 NOTE EXISTING CONDITIONS (TYPE OF WINDOW) FOR BEDROOMS,
 FBC R310, FBC EB 505.1. THE CLEAR OPENING CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE INSTALLATION SCHEDULE WHICH CAN
 BE FOUND AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/S
 CHEDULE_FOR_INSTALLATION.PDF OR IN THE CSD LOBBY. A
 COPY IS ALSO ATTACHED FOR YOUR CONVENIENCE.
  
 3. MULLION PRODUCT APPRPOVALS REQUIRED FOR THE DOUBLE
 WINDOWS, FAC9B72.
  
 4. PLEASE PROVIDE A VALUE OF WORK INCLUDING MATERIAL
 AND LABOR.
  
 5. PLEASE REVISE THE PERMIT DESCRIPTION AS IT IS
 ILLEGIBLE. NEW PLYWOOD AND STUCCO IS INDICATED ON THE
 APPLICATION (AS WELL AS WORDS I CAN'T READ). PLEASE
 PROVIDE A FLOOR PLAN SHOWING SCOPE AND A DETAIL SHOWING
 PROPOSED WORK.
  
  
  