| Plan Review Notes For Permit 09020115 |
| Permit Number |
09020115 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-03-04 13:53:29 | BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE | | | INFORMATION PRIOR TO INSPECTION TO AVOID ANY CONFLICTS | | | OR DELAYS): | | | | | | 1- REVISE CONSTRUCTION TYPE SPECIFIED ON SHEET TS-1. | | | SPECIFY CONSTRUCTION TYPE OF EXISTING OVERALL BUILDING, | | | NOT JUST THE PHARMACY AREA. | | | | | | 2- CLARIFY WHY PROVIDING 2 DIFFERENT WIND LOAD | | | CALCULATIONS. ONE FROM THE ARCHITECT AND THE OTHER ONE | | | FROM THE ENGINEER. CALCULATIONS DON'T MATCH EACH OTHER. | | | ENGINEER TO SIGN AND SEAL AND PROVIDE HIS INFORMATION | | | IN ALL SHEETS WITH ORIGINAL SIGNATURE AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTE. ARCHITECT TO SIGN AND SEAL | | | AND PROVIDE HIS INFORMATION IN ALL SHEETS AS REQUIRED | | | BY CHAPTER 481 FLORIDA STATUTE. | | | ***NOTE: ONLY NEED TO PROVIDE CALCULATIONS DONE BY ONE | | | DESIGN PROFESSIONAL. |
|