Plan Review Notes
Plan Review Notes For Permit 09020115
Permit Number 09020115
Review Stop M
Sequence Number 1
Notes
Date Text
2009-02-09 07:48:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A-4.0: THE CRUB/RTU ATTACHMENT DETAIL REFERENCES
 THE 2001 FBC AND SECTION 1511.7. THIS PROJECT WAS
 SUBMITTED UNDER THE 2004 FBC WITH 2007 SUPPLEMENTS.
 ALSO, THE CORRECT CODE SECTION FOR CURB HEIGHTS IS
 1509.7. PLEASE REFERENCE THE CORRECT CODE EDITION AND
 SECTIONS ON ALL AREAS OF PLANS.
  
 2. PG A-4.0 & M-2.0: THE CURB AND RTU INSTALLATION
 DETAILS SHOWN ON THESE PAGES (AND ATTACHED
 CALCULATIONS) ARE IN CONFLICT. WHICH IS CORRECT? PLEASE
 CLARIFY AND DEMONSTRATE COMPLIANCE WITH FBCM 301.13.
  
 3. PG M-2.0: DIFFUSER DETAIL ON THIS PAGE CALLS FOR 1"
 WIDE STRAP AS SUPPORT FOR THE FLEX DUCT. N NO CASE
 SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT IS IN
 DIRECT CONTACT WITH IT BE LESS THAN 1 1/2 INCHES WIDE
 IN ACCORDANCE WITH FBCM 603.5.6.6(6).
  
 4. PG M-2.0: DUCT DETECTOR DETAIL CALLS FOR AUDIBLE -
 VISIBLE NOTIFICATION TO BE IN A "NORMALLY OCCUPIED"
 LOCATION. THE SIGNALS ARE ACTUALLY REQUIRED TO BE IN AN
 APPROVED LOCATION IN ACCORDANCE WITH FBCM 606.4.1.
 CONSULT FIELD INSPECTOR TO DISCUSS AN APPROVED
 LOCATION.
  
 5. PG M-2.0: RTU DETAIL SAYS "SEE MECHANICAL PLAN" FOR
 CONTINUATION OF CONDENSATE DRAIN LINE. NO CONTINUATION
 COULD BE FOUND ON PLANS. CONDENSATE SHALL BE CONVEYED
 FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF
 DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO A STREET,
 ALLEY OR OTHER AREAS SO AS TO CAUSE A NUISANCE IN
 ACCORDANCE WITH FBCM 307.2.1. SHOW ON PLANS THE MEANS
 AND LOCATION OF CONDENSATE DISPOSAL FOR NEW RTU.
  
 6. WIND RESISTANCE: DETAILS AND CALCULATIONS FOR RTU
 CAND RTU CURB ATTACHMENT WERE PROVIDED (SEE COMMENT #2
 ABOVE), BUT NO DETAIL WAS PROVIDED FOR VENT CAPS OR
 VENT CAP CURBS. ALSO, NO INFORMATION WAS PROVIDED
 REGARDING THE WIND RESISTANCE CAPABILITIES OF THE RTU
 AND VENT CAPS THEMSELVES. EQUIPMENT AND APPLIANCES THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES AS DETERMINED IN ACCORDANCE WITH
 FBCM 301.13.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 AN EXPLANATION OF HOW EACH COMMENT WAS ADDRESSED AND A
 DESCRIPTION OF WHERE THE RELEVANT INFORMATION CAN BE
 FOUND.
  