Plan Review Notes
Plan Review Notes For Permit 09020115
Permit Number 09020115
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-02-09 13:00:11*****DENIED*****
  
  
 1. ON SHEET THE COVER SHEET (TS-1), AMEND EDITION OF
 THE FLORIDA FIRE PREVENTION CODE FROM 2004 TO 2007
 WHICH SHALL BE REFERENCED. THE 2007 EDITION IS BASED
 UPON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND NFPA
 1, UNIFORM FIRE CODE, 2006 EDITION.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. EXPLAIN AND/OR COORDINATE THE DISCREPANCY WITH THE
 NUMBER AND LOCATION OF EXIT AND EMERGENCY LIGHTS AS
 SHOWN ON L-S.1, A-4.0, AND E-2.0 SHEETS.
  
 4. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS TENANT SPACE IF SO EQUIPPED. SPRINKLER HEADS MAY
 BE SHOWN ON THE REFLECTED CEILING SHEET (A-4.0).
  
 5. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS
 TENANT SPACE IF SO EQUIPPED. FIRE ALARM DEVICES MAY BE
 SHOWN ON THE LIFE SAFETY SHEET (L-S.1).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722