| Plan Review Notes For Permit 09020115 |
| Permit Number |
09020115 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-09 07:19:19 | | | | | | | | | | APPLICATION #009020115 ELECTRICAL PLAN REVIEW | | | 2100 45TH STREET 2/6/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE | | | CALCULATION PROCEDURES. THIS CAN BE DEMONSTRATED ON THE | | | PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN | | | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. | | | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE | | | WITH THE ONES IN THE CALCULATIONS. SEE TABLE 13-415.2.B | | | | | | 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE | | | PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS. | | | | | | 3} LOCATE SPACE CONTROL DEVICE TYPES AND LOCATIONS ON | | | THE PLAN PER 13-415.1.ABC.1.2 SPACE CONTROL. | | | | | | 4} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. SEE ABOVE REFERENCES. SHEET TS-1 INCORRECTLY | | | REFERENCES THE 2001 & 2006 NEC . | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | | | | |
|