| 2009-05-04 13:31:48 | DENIED |
| | REFERENCE: |
| | FBC-2004 RESIDENTIAL |
| | FBC-2004 BUILDING |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS ARE REQUIRED |
| | PER SECTIONS 1503.6 & R320.7 AS WELL AS TABLES 1106.3 & |
| | 1106.7. |
| | ****RESPONSE NOTED, BUT THE GUTTER SIZE AND DRAIN SIZE |
| | ARE NOT INDICATED. ALSO INDICATE WHERE THE DOWNSPOUTS |
| | TERMINATE. SEE SECTION R320.7. |
| | |
| | 3. OK |
| | |
| | 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION |
| | 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND |
| | SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL |
| | DRAINS/SCUPPERS. (HEIGHT & WIDTH). |
| | *****RESPONSE NOTED, BUT SCUPPER SIZE IS NOT INDICATED |
| | ON THE PLANS. ALSO THE OVERFLOW SCUPPERS SHALL BE A |
| | MINIMUM OF 2" AND A MAXIMUM OF 4" ABOVE THE ROOF TO THE |
| | FLOW LINE OF THE SCUPPER. THE SOUTH ELEVATION INDICATES |
| | ALL SCUPPERS TO BE AT ROOF LEVEL. |
| | |
| | 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE |
| | CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE |
| | CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS & TABLES. |
| | ****RESPONSE NOTED, BUT THE UPPER ROOF ON THE CABANA |
| | APPEARS TO HAVE PARAPET WALLS AROUND THE ROOF AND AS |
| | SUCH REQUIRES FOOR DRAINS OR SCUPPERS PER SECTION |
| | R903.4. IN ORDER TO PROPERLY SIZE THE SCUPPERS |
| | INDICATED, CALCULATIONS ARE REQUIRED SHOWING THE TOTAL |
| | SQUARE FOOTAGE, (INCLUDING 1/2 THE AREA OF ALL PARAPET |
| | WALLS), AND TOTAL AREA BEING DRAIN BY EACH PRIMARY & |
| | SECONDARY SCUPPER. |
| | |
| | 6. OK |
| | |
| | 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC. |
| | SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1, |
| | P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7. |
| | ****RESPONSE, NOTED, BUT THE SANITARY ISOMETRIC RISER |
| | DIAGRAM FOR THE POOL HOUSE ON SHT P101 SHOWS A FLOOR |
| | DRAIN THAT IS NOT SHOWN ON THE FLOOR PLAN. PLEASE |
| | CORRELATE. ALSO INDICATE WHAT WILL BE DRAINING INTO THE |
| | FLOOR DRAIN. (INFORMATIONAL: FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE INTERCEPTORS. A FLOOR SINK OR |
| | HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2). ON |
| | SHT P200 RISER S/1 THE SINK SHALL NOT DRAIN THROUGH THE |
| | HORIZONTAL WET VENT FOR THE BATHROOM FIXTURES. SECTION |
| | 909.1. THE SINK SHALL DISCHARGE DOWNSTREAM OF THE |
| | BATHROOM FIXTURES. |
| | |
| | 8. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED AS ONE SET OF |
| | VOIDED SHEETS WAS NOT SUBMITTED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |