Plan Review Notes
Plan Review Notes For Permit 09020107
Permit Number 09020107
Review Stop P
Sequence Number 2
Notes
Date Text
2009-05-04 13:31:48DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 BUILDING
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS ARE REQUIRED
 PER SECTIONS 1503.6 & R320.7 AS WELL AS TABLES 1106.3 &
 1106.7.
 ****RESPONSE NOTED, BUT THE GUTTER SIZE AND DRAIN SIZE
 ARE NOT INDICATED. ALSO INDICATE WHERE THE DOWNSPOUTS
 TERMINATE. SEE SECTION R320.7.
  
 3. OK
  
 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION
 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND
 SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL
 DRAINS/SCUPPERS. (HEIGHT & WIDTH).
 *****RESPONSE NOTED, BUT SCUPPER SIZE IS NOT INDICATED
 ON THE PLANS. ALSO THE OVERFLOW SCUPPERS SHALL BE A
 MINIMUM OF 2" AND A MAXIMUM OF 4" ABOVE THE ROOF TO THE
 FLOW LINE OF THE SCUPPER. THE SOUTH ELEVATION INDICATES
 ALL SCUPPERS TO BE AT ROOF LEVEL.
  
 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE
 CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLES.
 ****RESPONSE NOTED, BUT THE UPPER ROOF ON THE CABANA
 APPEARS TO HAVE PARAPET WALLS AROUND THE ROOF AND AS
 SUCH REQUIRES FOOR DRAINS OR SCUPPERS PER SECTION
 R903.4. IN ORDER TO PROPERLY SIZE THE SCUPPERS
 INDICATED, CALCULATIONS ARE REQUIRED SHOWING THE TOTAL
 SQUARE FOOTAGE, (INCLUDING 1/2 THE AREA OF ALL PARAPET
 WALLS), AND TOTAL AREA BEING DRAIN BY EACH PRIMARY &
 SECONDARY SCUPPER.
  
 6. OK
  
 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC.
 SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1,
 P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7.
 ****RESPONSE, NOTED, BUT THE SANITARY ISOMETRIC RISER
 DIAGRAM FOR THE POOL HOUSE ON SHT P101 SHOWS A FLOOR
 DRAIN THAT IS NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO INDICATE WHAT WILL BE DRAINING INTO THE
 FLOOR DRAIN. (INFORMATIONAL: FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE INTERCEPTORS. A FLOOR SINK OR
 HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2). ON
 SHT P200 RISER S/1 THE SINK SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENT FOR THE BATHROOM FIXTURES. SECTION
 909.1. THE SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES.
  
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE, COMMENT NOT ADDRESSED AS ONE SET OF
 VOIDED SHEETS WAS NOT SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  