Plan Review Notes
Plan Review Notes For Permit 09020107
Permit Number 09020107
Review Stop G
Sequence Number 2
Notes
Date Text
2009-05-04 14:12:23DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS.
 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ****RESPONSE NOTED, BUT THE PIPE SIZE FOR THE GENERATOR
 & TANKLESS WATER HEATER, (989MBTU), REQUIRES 1-1/2"
 GALVANIZED THRU THE SHUT OFF VALVE FOR THE GENERATOR.
 3/4" IS SHOWN. TABLE G2413.4(1) @ 30 FEET.
  
 3. OK
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU LOAD INDICATED ON THE
 ISOMETRIC RISER DIAGRAM FOR THE GENERATOR, (748MBTU),
 DOES NOT REFLECT THE MANUF. SUBMITTAL, (790MBTU). ALSO
 THE ISOMETRIC INDICATES THE TANKLESS WATER HEATERS AS
 240MBTU, BUT THE MANUF SHEETS INDICATE THEM AT 199MBTU.
 PLEASE CORRELATE. TOTAL BTU'S ON THE SYSTEM IS 1588MBTU
 WITH ADJUSTMENTS. PLEASE INDICATE ON RISER DIAGRAM.
  
 5. OK
 6. OK
 8. OK
 9. OK
  
 ****NEW COMMENT****
  
 1B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 LISTED REGULATORS. INDICATE THE MODEL NUMBERS AND SHOW
 THE CAPACITY MULTIPLE APPLIANCE FOR EACH REGULATOR.
 UNIONS ARE REQUIRED PAST THE SHUT OFF VALVES FOR THE
 REGULATORS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  