| Date |
Text |
| 2009-05-04 14:12:23 | DENIED |
| | REFERENCE: |
| | FBC-2004 RESIDENTIAL |
| | FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS. |
| | SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE |
| | FOLLOWING INFORMATION FOR REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | ****RESPONSE NOTED, BUT THE PIPE SIZE FOR THE GENERATOR |
| | & TANKLESS WATER HEATER, (989MBTU), REQUIRES 1-1/2" |
| | GALVANIZED THRU THE SHUT OFF VALVE FOR THE GENERATOR. |
| | 3/4" IS SHOWN. TABLE G2413.4(1) @ 30 FEET. |
| | |
| | 3. OK |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ****RESPONSE NOTED, BUT THE BTU LOAD INDICATED ON THE |
| | ISOMETRIC RISER DIAGRAM FOR THE GENERATOR, (748MBTU), |
| | DOES NOT REFLECT THE MANUF. SUBMITTAL, (790MBTU). ALSO |
| | THE ISOMETRIC INDICATES THE TANKLESS WATER HEATERS AS |
| | 240MBTU, BUT THE MANUF SHEETS INDICATE THEM AT 199MBTU. |
| | PLEASE CORRELATE. TOTAL BTU'S ON THE SYSTEM IS 1588MBTU |
| | WITH ADJUSTMENTS. PLEASE INDICATE ON RISER DIAGRAM. |
| | |
| | 5. OK |
| | 6. OK |
| | 8. OK |
| | 9. OK |
| | |
| | ****NEW COMMENT**** |
| | |
| | 1B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | LISTED REGULATORS. INDICATE THE MODEL NUMBERS AND SHOW |
| | THE CAPACITY MULTIPLE APPLIANCE FOR EACH REGULATOR. |
| | UNIONS ARE REQUIRED PAST THE SHUT OFF VALVES FOR THE |
| | REGULATORS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |